Installation Instructions - ADEMCO VISTA-20P Installation And Setup Manual

Hide thumbs Also See for VISTA-20P:
Table of Contents

Advertisement

Installation Instructions

PROMPT
10 Zone Type
Perimeter
03
10 Partition
1
10 Report Code
1st 01 2nd 00 10
02 HARDWIRE TYPE
EOL
0
02 Response Time
1
10 INPUT TYPE
RF TRANS
3
5-2
VALID ENTRIES
Zone Type (ZT)
00-24, 77, 90, 91 = zone type
(see table at right; types 92/93
only programmable via
downloader)
Partition No. (P)
1-3 = partition (3 = common)
[ ∗ ] to continue
Report Code (RC)
First Digit: 1-9, #+10 for 0, #+11
for B, #+12 for C,
#+13 for D, #+14 for
E, #+15 for F
00 to disable
Second Digit: same as above
[ ∗ ] to continue
Hardwire Type
0 = EOL
3 = zone doubling
1 = NC
4 = double-balanced
2 = NO
[ ∗ ] to continue
Response Time (RT)
0 = 10mSec
1 = 350mSec
2 = 700mSec
3 = 1.2 seconds
[ ∗ ] to continue
Input Device type (In)
2 = AW (Aux wired zone)
3 = RF (supervised RF
transmitter,
4 = UR (unsupervised RF
transmitter)
5 = Button type RF transmitter
(unsupervised).
[ ∗ ] to continue
EXPLANATION
Each zone must be assigned to a zone type, which defines the way in
which the system responds to faults in that zone.
Enter the Zone Type code from the list below:
Note: If 00 is entered, Delete Zone ? will be displayed.
00 = Not used
01 = Entry/exit #1
02 = Entry/exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night 14 = Carbon Monoxide 77 = Keyswitch
06 = 24-Hr Silent
*5800 button-type transmitters only
VISTA-20P only.
Enter the Partition number for this zone. Partition 1 is shown
entered.
Enter the report code for this zone, which consists of 2 hexadecimal
digits, each in turn consisting of 2 numerical digits. For example, for
a report code of "10," enter 01 and 00.
®
For Contact ID
, entering any non-zero entry as the first digit
enables the report code for this zone. Refer to the System
Communication section for information about report codes and
formats.
This prompt appears only for zone numbers 02-08.
Zone 1 is automatically set for EOL operation.
† VISTA-20P only
This prompt appears only for hard-wired zones 01-08 (zone 02 is used
as an example in display).
Option 3: used for "clean me" option on zone 1 (see field ∗174).
This prompt is skipped if zone-doubling was enabled at "Hardwire
Type" prompt.
All of the RF transmitters have one or more unique factory-assigned
input (loop) ID codes. Each of the inputs requires its own
programming zone (e.g., a 5804's four inputs require four
programming zones).
RF Transmitters can be enrolled as one of the following types:
Type
Description
"RF"
Sends periodic check-in signals, as well as
(Supervised RF)
fault, restore, and low-battery signals. The
transmitter must stay within receiver's range.
"UR"
Sends all the signals that the "RF" type
(Unsupervised RF)
does, but the control does not supervise the
check-in signals. The transmitter may therefore
be carried off-premises.
"BR" (Unsupervised Sends only fault signals. It will not send a
Button RF)
low-battery signal until it is activated. The
transmitter may be carried off-premises.
Note: For the built-in hardwired zones, the Input Device type is
automatically displayed as HW and cannot be edited.
07 = 24-Hr Audible
20 = Arm–STAY*
08 = 24-Hr Aux
21 = Arm–AWAY*
09 = Fire
22 = Disarm*
23 = No Alarm Resp*
10 = Interior w/Delay
12 = Monitor Zone
24 = Silent Burglary
16 = Fire w/Verify
90-93 = Configurable

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-20pcnVista-15pVista-15pcn

Table of Contents