The only two valid fan configurations are listed in the following table.
Configuration
Fan bay 1 Fan bay 2 Fan bay 3
Fan blank
1 processor
Fan
2 processors
For a single-processor configuration, five fans and two blanks are required in specific fan bays for
redundancy.
For a dual-processor configuration, seven fans are required for redundancy. A fan failure or missing fan
causes a loss of redundancy. A second fan failure or missing fan causes an orderly shutdown of the server.
The high performance fan option might be necessary for the following installations:
•
LR DIMM configuration
•
ASHRAE compliant configurations
For more information, see the HP website (http://www.hp.com/servers/ASHRAE).
The server supports variable fan speeds. The fans operate at minimum speed until a temperature change
requires a fan speed increase to cool the server. The server shuts down during the following
temperature-related scenarios:
•
At POST and in the OS, HP iLO performs an orderly shutdown if a cautionary temperature level is
detected. If the server hardware detects a critical temperature level before an orderly shutdown occurs,
the server performs an immediate shutdown.
•
When the Thermal Shutdown feature is disabled in RBSU, HP iLO does not perform an orderly shutdown
when a cautionary temperature level is detected. Disabling this feature does not disable the server
hardware from performing an immediate shutdown when a critical temperature level is detected.
CAUTION:
A thermal event can damage server components when the Thermal Shutdown feature
is disabled in RBSU.
Fan blank
Fan
Fan
Fan
Fan bay 4 Fan bay 5 Fan bay 6
Fan
Fan
Fan
Fan
Fan
Fan
Component identification 19
Fan bay 7
Fan
Fan