Code Indication On Remote Controller; Wall Mounted/Floor Standing Type; Duct Concealed/Ceiling Cassette Type - Daikin 2MXS-W Series Service Manual

Multi-split type air conditioners
Table of Contents

Advertisement

Code Indication on Remote Controller

4. Code Indication on Remote Controller

4.1

Wall Mounted/Floor Standing Type

Codes
4.2

Duct Concealed/Ceiling Cassette Type

Codes
Note
When there is a possibility of open phase power supply, also check power supply.
154
Error
00
Normal condition
A1
Indoor unit PCB abnormality
A5
Freeze-up protection control/heating peak-cut control
A6
Indoor fan motor (DC motor) or related abnormality
C4
Indoor heat exchanger thermistor or related abnormality
C7
Front panel open/close fault (FTXR series)
C9
Room temperature thermistor or related abnormality
U4
Signal transmission error (between indoor unit and outdoor unit)
UA
Mismatching of indoor unit and outdoor unit
Error
00
Normal condition
A1
Indoor unit PCB abnormality
A3
Drain level control system abnormality
Indoor fan motor (DC motor) or related abnormality
A6
(See the Note below)
A8
Indoor fan PCB abnormality
AF
Humidifier or related abnormality
C4
Indoor heat exchanger thermistor 1 or related abnormality
C5
Indoor heat exchanger thermistor 2 or related abnormality
C9
Room temperature thermistor or related abnormality
CE
Presence sensor or floor sensor abnormality
CJ
Remote controller thermistor abnormality
U4
Signal transmission error (between indoor unit and outdoor unit)
U5
Signal transmission error (between indoor unit and remote controller)
Signal transmission error (between MAIN remote controller and SUB
U8
remote controller)
UA
Mismatching of indoor unit and outdoor unit
Description
Description
SiUS122226E
Reference
Page
156
158
159
162
163
162
164
167
Reference
Page
168
169
170, 172
175
176
177
177
177
178
179
180
182
183
184
Part 6 Service Diagnosis