Ionization Current - Buderus LOGANO PLUS GB312 Installation Instructions Manual

Gas condensing boiler
Table of Contents

Advertisement

Display
1)
Type
code
Fault code
K
6A
577
L
6L
561
K
7A
550
Table 22 Fault messages
1) V = locking; B = inhibiting; BC = operating code
Logano plus GB312 – 6 720 647 367 (2012/11)
Cause
Description
No flame detected within

Ionization current

the safety period.
< 1.1 μA during safety
period.
5 power-up sequences
The burner control unit
(power supply
has switched off 5 times
disconnection during burner
during the burner start-
start-up).
up sequence.
Voltage too low.
The power supply
voltage is too low.
Troubleshooting
Testing sequence/
Cause
Measure
Gas supply/dynamic
If pressure too low,
pressure too low.
inform gas company.
Gas pressure regulator
Fit gas pressure
not set to required gas
regulator adjusted to
flow rate.
required gas flow rate;
inform gas company if
necessary.
Cross-sectional area of
Fit adequately
gas pipe insufficient (min.
dimensioned gas piping
cross-sectional area of
gas supply pipe).
Air in gas pipe.
Bleeding the gas supply
pipe
Excessively high flue
Fit properly
system backpressure
dimensioned and
through unfavorable
configured flue system.
layout (too many
diversions; cross-section
inadequate or too long;
horizontal sections too
long).
Ignition/ionization
Clean/replace ignition/
electrode dirty
ionization electrode.
Check connecting lead
Establish good electrical
between SAFe and
contact. Replace lead if
ionization electrode for
necessary.
poor contact, breaks and
damage.
Check electrode gaps and
Align burner rod/
ignition/ionization
electrode. Replace
electrode for damage.
defective electrode.
Check connecting lead
Establish good electrical
between ignition
contact.
transformer and ignition
If necessary, replace
electrode for poor
line.
contact (at electrode and
transformer), breaks and
damage.
SAFe burner control unit
Replace SAFe.
defective.
Ignition transformer
Replace ignition
defective (delayed or
transformer.
non-existent spark,
"violent" starttup).
Check the 120V power
Reset burner control
supply to the control unit.
unit.
Rectify power supply
problem.
The power supply voltage
Ensure adequate power
must not drop below
supply voltage.
102V.
10
57