Buderus LOGANO PLUS GB312 Installation Instructions Manual page 60

Gas condensing boiler
Table of Contents

Advertisement

10
Troubleshooting
Display
1)
Type
code
Fault code
L
CO
569
L
CY
573
L
CY
574
L
LP
570
L
LL
571
Table 22 Fault messages
1) V = locking; B = inhibiting; BC = operating code
60
Cause
Description
Water pressure sensor fault
Water pressure sensor
(short circuit).
short circuit (voltage
< 0.5 V).
Flow temperature
The control unit receives
unrealistic values from
< 23 °F (< -5 °C)
the flow temperature
(circuit break)
sensor.
Flow temperature
The control unit receives
unrealistic values from
>266°F (>130°C)
the flow temperature
(short circuit)
sensor.
Too many resets via the
Too many resets have
interface.
been received via the
interface within a certain
period.
Important: this fault can
only be reset by the
button on the SAFe.
Too many restarts despite
15 directlly consecutive
resetting.
restarts have taken
place. In other words,
the same problem was
still present after
resetting.
Important: this fault can
only be reset by the
button on the SAFe.
Testing sequence/
Cause
Measure
Check connecting lead to
Rectify any short
water pressure sensor.
circuits.
Check water pressure
Replace water pressure
sensor.
sensor.
Check cabling between
Replace connecting lead
SAFe and return sensor.
if necessary
Check electrical
Rectify any contact
connection of connecting
problems
lead to SAFe.
Check resistance levels of
Replace temperature
temperature sensor
sensor if necessary
against table
Check voltage at
If temperature sensor
temperature sensor
resistances are correct
terminals on SAFe against
but voltages incorrect,
table
replace SAFe
Check cabling between
Replace connecting lead
SAFe and return sensor.
if necessary
Check electrical
Rectify any contact
connection of connecting
problems
lead to SAFe.
Check resistance levels of
Replace temperature
temperature sensor
sensor if necessary
against table
Check voltage at
If temperature sensor
temperature sensor
resistances are correct
terminals on SAFe against
but voltages incorrect,
table
replace SAFe
Faults have continually
Identify and eliminate
been simply reset and not
the cause of the problem
rectified.
causing the resets.
There is a fault on the
Replace BC10.
BC10 causing continual
resets.
There is a malfunction on
Replace SAFe.
the SAFe.
Faults have continually
Identify and eliminate
been simply reset and not
the cause of the problem
rectified.
causing the resets.
Logano plus GB312 – 6 720 647 367 (2012/11)