Buderus LOGANO PLUS GB312 Installation Instructions Manual page 59

Gas condensing boiler
Table of Contents

Advertisement

Display
1)
Type
code
Fault code
L
8Y
591
L
9Y
500
501
502
503
L
CY
566
L
CY
567
L
CO
568
Table 22 Fault messages
1) V = locking; B = inhibiting; BC = operating code
Logano plus GB312 – 6 720 647 367 (2012/11)
Cause
Description
Error checking safety
SAFe pressure switch
assembly.
has not tripped.
Internal SAFe relay fault.
Internal electronic fault
on SAFe.
Return temperature
The control unit receives
unrealistic values from
< 23 °F (< -5 °C)
the return sensor.
(circuit break)
Return temperature
Control unit is receiving
implausible signals from
> 266 °F (> 130 °C)
return sensor.
(short circuit)
Water pressure sensor fault
Water pressure sensor
(break in cable).
circuit break (voltage
> 3.5 V)
Troubleshooting
Testing sequence/
Cause
Measure
Check whether gas
Ensure gas supply
supply pressure is
pressure is
> 3 inches w.c.
> 3 inches w.c.
Check setting of SAFe
Adjust setting of SAFe
pressure switch.
pressure switch to
3 inches w.c.
Check connector on gas
Insert connector
valve is properly seated.
properly.
Replace SAFe pressure
switch and wiring.
Replace SAFe.
Press Reset button and
If fault recurs after reset,
wait to see if fault is
SAFe must be replaced.
eliminated.
Check cabling between
Replace connecting lead
SAFe and return sensor.
if necessary.
Check electrical
Rectify any contact
connection of connecting
problems.
lead to SAFe.
Check resistance levels of
Replace temperature
temperature sensor
sensor if necessary.
against table.
Check voltage at
If temperature sensor
temperature sensor
resistances are correct
terminals on SAFe against
but voltages incorrect,
table.
replace SAFe.
Check cabling between
Replace connecting lead
SAFe and return sensor.
if necessary.
Check electrical
Rectify any contact
connection of connecting
problems.
lead to SAFe.
Check resistance levels of
Replace temperature
temperature sensor
sensor if necessary.
against table.
Check voltage at
If temperature sensor
temperature sensor
resistances are correct
terminals on SAFe against
but voltages incorrect,
table.
replace SAFe.
Check connection
Establish good electrical
between SAFe and water
contact. Replace lead if
pressure sensor for poor
necessary.
contact, breaks and
damage.
Check water pressure
Replace water pressure
sensor.
sensor.
10
59