Installing The Boiler; Boiler Room Requirements; Recommended Wall Clearances; Leveling The Boiler - Buderus LOGANO PLUS GB312 Installation Instructions Manual

Gas condensing boiler
Table of Contents

Advertisement

4

Installing the boiler

This section explains how to erect and position the boiler correctly in the
boiler room.
4.1

Boiler room requirements

WARNING: Risk of system damage due to freezing!
▶ Install the heating system in a frost-free room.
DANGER: Dangers posed by explosive and easily
combustible materials.
▶ Do not use or store easily-combustible materials
(paper, lace curtains, clothing, thinners, paints, etc.)
near the boiler.
▶ Maintain a clearance of 16 inches from the boiler.
WARNING: Risk of boiler damage from contaminated
combustion air!
▶ Do not use cleaning agents that contain chlorine or
halogenated hydrocarbons (e.g. in spray cans,
solvents and cleaning agents, paints, glues).
▶ Do not store or use such substances in the boiler
room.
▶ Avoid excessive dust accumulation (building dust) on
or near the boiler.
4.2

Recommended wall clearances

When determining the installation location, take the clearances for the
flue and the connection pipe assembly into consideration ( Fig. 9 and
Section 6, flue system connection and the pipework on the water and
gas sides).
Dimension
A
1)
B
C
D
1)
E
Table 5 Recommended and minimum wall clearances (dimensions in
inches). Minimum clearance dimension E must absolutely be
adhered to.
1) This clearance dimension is dependent on the flue system fitted
Where applicable, allow extra wall clearances for
additional components, for example indirect water
storage tanks, pipe connections or other components on
the flue gas side etc.
Logano plus GB312 – 6 720 647 367 (2012/11)
Wall clearance (inch)
Minimum
Recommended
20
28
22
28
20
28
20
28
6
14
D
B
Fig. 9 Wall clearances in the boiler room
4.3

Leveling the boiler

To prevent air collecting in the boiler and to allow the condensate to
drain freely from the condensate pan, the boiler must be leveled.
CAUTION: Risk of boiler damage due to inadequate
load-bearing capacity of floor or unsuitable base.
▶ Make sure that the surface on which the boiler stands
has sufficient load-bearing capacity.
▶ The boiler may stand on a base made of combustible
material but not on carpet.
▶ Place the boiler in its final position.
▶ Level the boiler horizontally by turning the adjustable feet and using a
spirit level.
Fig. 10 Leveling the boiler
[1]
Adjustable feet
[2]
Level
4
Installing the boiler
E
C
A
7 747 010 720-09.1RS
7 747 010 720-10.1RS
15