Heating system inspection
▶ Check all joints on the gas valve for leaks using a suitable leak
detecting agent.
Turn on the gas isolating valve D on the outlet side of the gas valve
again. Reset the boiler to normal operating mode.
Fig. 71 Testing apparatus set-up for gas valve leak testing
[A]
Main isolating valve on gas valve inlet side
[B]
Solenoid valve 1
[C]
Solenoid valve 2
[D]
Gas isolating valve on gas valve outlet side
[E]
Manual isolating valve (testing apparatus)
[F]
Manual isolating valve (testing apparatus)
[G]
Hand pump (testing apparatus)
[H]
Pressure tester (testing apparatus)
[I]
Low pressure switch (available separately)
[1, 2, 3, 4, P]Pressure testing points