Facp With Keltron - Fire-Lite MS-9200UDLS User Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

FACP with Keltron

APPENDIX D
The following figure illustrates the connections between the FACP and Keltron Receiver/
Transmitter.
CAUTION! For reasons of wiring diagram clarity, terminal designations of Keltron modules are
not shown in actual order. Follow Keltron manual and module markings for exact terminal
locations to prevent severe module damage!
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
Sprinkler Supervisory Signal
204
FACP with Keltron
Alarm/Trouble Signal
4XTMF Module
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Fire Alarm Control Panel
(terminal blocks are not shown in
their actual positions in order to
clarify wiring connections.
*Note: For more
information, refer
to Keltron manual.
24 VDC nonresettable power
MS-9200UDLS PN 52750:E1
01/27/09

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200udlse

Table of Contents

Save PDF