Electrical Specifications
shielded wire for any non-SLC-loop wiring entering or exiting the cabinet that is not enclosed in
conduit. Use twisted-pair unshielded wiring for SLC-loop wiring.
NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce
problems by exclusively using electronic sounders (such as the MA/SS-24 Series) instead of
more electronically noisy notification appliances (such as electromechanical bells or horns).
Circuit Type
Circuit Function
SLC
Connects to
(power limited)
intelligent and
addressable
modules.
or
or
EIA-485 ACS
Connects to ACS
Connection
devices such as
(power limited)
annunciators and
UDACT
EIA-485 RDP
Connects to RDP
Connection
devices such as
(power limited)
LCD-160
EIA-232
Connects to Printers
(power limited)
or PC.
IDC
M300MJ, M301MJ
Initiating Device
XP5-M (power
Circuit
limited)
NAC
XP5-C, M300CJ
Notification
(power limited)
Appliance
Circuit
24 VDC Power
To TM-4 Transmitter,
Runs
Annunciator and
(power-limited)
M300CJ modules
CHG-120
External battery
charger
*
Notifier brand cable is recommended; see the product catalog available from Paige Electric.
64
Wire Requirements
Twisted-unshielded pair, 12 to 18
2
AWG (3.25 to 0.75mm
). 50 ohms,
maximum per length of Style 6 & 7
loops. 50 ohms per branch
maximum for Style 4 loop.
Twisted-shielded pair.
Untwisted, unshielded wire, in
conduit or outside of conduit.
Twisted-shielded pair with a
characteristic impedance of 120
2
ohms. 18 AWG (0.75mm
)
minimum.
Twisted-shielded pair with a
characteristic impedance of 120
2
ohms. 18 AWG (0.75mm
)
minimum.
Twisted-shielded pair. 18 AWG
2
(0.75mm
) minimum.
12-18 AWG
Maximum circuit resistance is
20 ohms.
12-18 AWG. MPS-24A: At alarm
current level, no more than a 1.2 V
drop at the end of the circuit, or
sized to provide the minimum rated
operating voltage of the appliances
used.
12-18 AWG. Size wire so that no
more than 1.2 V drop across wire
run from supply source to end of any
branch.
12 AWG in conduit
Table A.1 Wire Requirements
IFC-3030 Installation Manual — P/N 52024:C 08/05/2005
Distance
Typical Wire Type
(feet/meters)
12,500 ft (3,810 m)
12 AWG
9,500 ft. (2,895.6 m)
14 AWG
6,000 ft. (1,828.8 m)
16 AWG
3,700 ft. (1,127.76 m)
18 AWG
10,000 ft (3048 m)
12 AWG
1,000 ft (304.8 m)
12 to 18 AWG
6,000 ft (1829 m)
16 AWG/1.30mm
(max)
4,000 ft (1219 m)
16 AWG/1.30mm
(max)
50 ft (15.24 m)
16 AWG/1.30mm
without modem
12 to 18 AWG
(3.25 to 0.75mm
To meet 1.2 V drop, or
12 to 18 AWG
sized to provide the
(3.25 to 0.75mm
minimum rated operating
voltage of the appliances
used.
To meet 1.2 volt drop
12 to 18 AWG
(3.25 to 0.75mm
20 ft (6.1 m)
12 AWG
maximum
(3.25mm
Wire Requirements
*
2
2
2
2
)