3.12.3 Field Wiring an Auxiliary Relay Module
The figure above shows terminal assignments for ARM-4 module control relays K1-K4, which
control non-power-limited circuits. Power-limited and non-power-limited circuit wiring must
remain separated by at least 0.25 inch (6.35 mm) within the cabinet and exit the cabinet though
different knockouts, conduits, or both. Refer to Section 3.16 "UL Power-limited Wiring
Requirements".
The table contains contact ratings for relays K1-K4 on the ARM-4 module:
Resistive Load
125 VAC
30 VDC
Table 3.2 Contact Ratings for K1-K4 on the ARM-4 Module

3.13 Notification Appliance Circuit Current Limitations

The total current available from any group of Indication Appliance
Circuits cannot exceed 3.0 amps; this is limited to 1.0 amps if
AMPS-24 is the only power source. Figure 3.18 illustrates some of the
typical power supply/ Notification Appliance Circuit configurations.
Auxiliary
Power
J5 ICM-4RK
Supply
Auxiliary
Power
Supply
J5
ICM-4RK
J6
Auxiliary
Power
Supply
For this particular configuration (using
JP1
two auxiliary power supplies to power
JP2
on ICM-4RK or ICE-4), cut jumper JP1
and JP2 located above J5 and J6.
JP6
JP5
icejump.cdr
NOTE: The term "total" in these figures assumes that no Notification Appliance power is drawn
for any other purpose.
36
Contacts
Normally Open (N.O.) Normally Closed (N.C.)
20 A
20 A
These four Notification
Appliance Circuits
share the total current
provided by the
auxiliary power supply
These two Notification
Appliance Circuits
share the total current
provided by the
auxiliary power supply
These two Notification
Appliance Circuits
share the total current
provided by the
auxiliary power supply
Figure 3.18 Typical Supply/Notification Circuit Configurations
Notification Appliance Circuit Current Limitations
10 A
10 A
Auxiliary
J5
Power
ICM-4RK
J6
Supply
J5
ICE-4
Auxiliary
J5 ICM-4RK
Power
Supply
Auxiliary
J5
Power
ICE-4
Supply
IFC-3030 Installation Manual — P/N 52024:C 08/05/2005
J5 J6
(ICM-4RK)
J5 J6
(ICE-4)
Bottom wire of the
ICM-4RK/ICE-4
These eight Notification
Appliance Circuits
share the total current
provided by the
auxiliary power supply
These four Notification
Appliance Circuits
share the total current
provided by the
auxiliary power supply
These four Notification
Appliance Circuits
share the total current
provided by the
auxiliary power supply

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IFC-3030 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents

Save PDF