Grounding The Switch With A Grounding Conductor Buried In The Earth Ground; Grounding The Switch By Using The Ac Power Cord - H3C S5500-HI Switch Series Installation Manual

S5500-hi switch series
Hide thumbs Also See for S5500-HI Switch Series:
Table of Contents

Advertisement

Grounding the switch with a grounding conductor buried in the
earth ground
If the installation site has no grounding strips, but earth ground is available, hammer a 0.5 m (1.64 ft) or
longer angle iron or steel tube into the earth ground to serve as a grounding conductor.
The dimensions of the angle iron must be at least 50 × 50 × 5 mm (1.97 × 1.97 × 0.20 in). The steel tube
must be zinc-coated and its wall thickness must be at least 3.5 mm (0.14 in).
Weld the yellow-green grounding cable to the angel iron or steel tube and treat the joint for corrosion
protection.
Figure 29 Grounding the switch by burying the grounding conductor into the earth ground
(1) Grounding screw
(4) Earth

Grounding the switch by using the AC power cord

If the installation site has no grounding strips or earth ground, you ground an AC-powered switch through
the PE wire of the power cord. Make sure:
The power cord has a PE terminal.
The ground contact in the power outlet is securely connected to the ground in the power distribution
room or on the AC transformer side.
The power cord is securely connected to the power outlet.
NOTE:
If the ground contact in the power outlet is not connected to the ground, report the problem and reconstruct
the grounding system.
(2) Chassis rear panel
(5) Joint
22
(3) Grounding cable
(6) Grounding conductor

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents