Figure 12 Connecting the grounding cable to a grounding strip
(1) Grounding post
(3) Grounding cable
Grounding the switch with a grounding conductor buried in
the earth ground
If the installation site has no grounding strips, but earth ground is available, hammer a 0.5 m (1.64 ft)
or longer angle iron or steel tube into the earth ground to serve as a grounding conductor.
The dimensions of the angle iron must be a minimum of 50 × 50 × 5 mm (1.97 × 1.97 × 0.20 in). The
steel tube must be zinc-coated and its wall thickness must be a minimum of 3.5 mm (0.14 in).
Weld the yellow-green grounding cable to the angel iron or steel tube and treat the joint for corrosion
protection.
Figure 13 Grounding the switch by burying the grounding conductor into the earth ground
(1) Grounding screw
(4) Earth
(2) Grounding strip
(4) Hex nut
(2) Chassis rear panel
(5) Joint
12
(3) Grounding cable
(6) Grounding conductor