Manual Reset Error Codes-A##A (Or Locking Error Codes) - Harsco Industrial C1500H Installation & Owner's Manual

Gas fired boiler natural gas/propane/dual fuel
Hide thumbs Also See for C1500H:
Table of Contents

Advertisement

5.7
M
ANUAL RESET ERROR CODES
A Code Error
A01
IGNIT ERROR
A02
TOO MANY FLAME FAILURES
A03
T MAX LOCK ERROR
A05
GV RELAY ERROR
A06
SAFTEY RELAY ERROR
A09
RAM ERROR
A09
FLAG BYTE INTEGRITY ERROR
A09
AD HI CPL ERROR
A09
AD LO CPL ERROR
A09
REGISTER ERROR
A10
E2PROM ERROR
A12
WRONG EEPROM SIGNATURE
A13
STATE ERROR
A14
ROM ERROR
A15
15MS XRL ERROR
A16
20 MS XLR ERROR
A18
STACK ERROR
A19
FLAME OUT TOO LATE ERROR
A20
FLAME ERROR I
A30
HIGH GAS PRESSURE ERROR
A31
LOW GAS PRESSURE ERROR
A32
41MS ERROR
A33
FAN ERROR
A34
AIR PRESS SW NOT OPEN ERROR
A35
AIR PRESS SW NOT CLOSED ERROR
A37
UV SENSOR BROKEN
A38
MOD BACK DIFF ERROR
A39
RAPID RISE ERROR LOCK RET
A40
RAPID RISE ERROR LOCK FLOW
A41
RAPID RISE ERROR LOCK HX
A43
LOW WATER CUTOFF ERROR
A44
FLAME CKT ERROR
NOTICE! When an Internal Error occurs, as identified above, the failure is internal to the ENVI
replacement of the ENVI
-A##A (OR LOCKING ERROR CODES)
®
control is required. A qualified service technician must replace the ENVI
Int. nr
Description
1
Three unsuccessful ignition attempts in a row
24
Three times flame was lost during on demand
18
Overheat stat is open
Problems with gas valve relay= internal hardware error
5
(pump not running)
Problems with gas valve relay = internal hardware error
6
(pump not running)
9
Internal software error
27
Internal software error
28
Internal software error
29
Internal software error
33
Internal software error
12
No communication with E2prom
10
Contents of Eprom is not up-to-date
13
Internal software error
14
Internal software error
16
Internal software error
22
Internal software error
19
Internal software error
20
Flame still present 10 sec. after closing the gas valve
21
Flame detected just before gas valve opened
32
Gas pressure is to high
31
Gas pressure is to low
23
Internal software issue
Fan deviation more than300 rpm longer than 1 minute (when fan
8
speed > 4200 rpm this error is ignored)
25
Air pressure switch doesn't open within 30 seconds
26
Air pressure switch doesn't close within 30 seconds
11
UV scanner not functioning
4
Large difference between return and flow temperatures
15
Return temperature rise too rapidly
7
Flow temperature rise to rapidly
17
Heat exchanger rise to rapidly
30
Water pressure is to low
34
Ionization (flame rod)wire lost for more than 15 seconds
53
®
MACH
Gas Fired Boiler
®
control and
®
control.

Advertisement

Table of Contents
loading

This manual is also suitable for:

C2000hC2500C3000C4000

Table of Contents