6.1.10 Terminal Block Assignments – Power Block
®
The MACH
C1500H/C2000H/C2500 boiler power is connected on the front top right side in Terminal box 2 or TB2 on
terminals 1, 2,and 8. Pictured below
®
The MACH
C3000/C4000 boiler power block is located in the junction box in the front of the boiler, at the lower left
corner (pictured to the right). This junction box houses the transformer, the fuses, the power block terminal strip
circuit breakers, and the blower relay.
The three space terminal strip circuit breakers are mounted on DIN rail and are for connection of the three power
wires. There is an additional space on the DIN rail for a ground connection. This boiler requires either 208-240 V,
three phase, 60 Hz or 480 V, three phase, 60 Hz. The boiler requires a dedicated ground wire. Do not ground
through the conduit.
Field service power connections
for C1500H/C2000H and C2500
Field service power
connections for C3000
and C4000
65
®
MACH
POWER INPUT JUNCTION BOX
Gas Fired Boiler