Harsco Industrial C1500H Installation & Owner's Manual page 30

Gas fired boiler natural gas/propane/dual fuel
Hide thumbs Also See for C1500H:
Table of Contents

Advertisement

RECOMMENDED GAS PIPING INSTALLATION
Gas
Remote Gas
Supply
Shutoff
Drip Leg
Meter
Field Gas Piping
NOTICE! See Pipe Capacity for Natural Gas chart on the following page for required pipe size, based on
overall length of pipe from meter plus equivalent length of all fittings. Approximate sizing may be based on 1 cubic
foot of natural gas per 1,000 Btu per hour input, i.e., 3,000,000 Btu per hour requires about 3,000 cubic feet per hour.
(See "Typical Boiler Operating Conditions," Section 4.4 for more information.)
Pipe Capacity for Natural Gas
Nominal
Iron Pipe
Internal
Size
Diameter
(Inches)
(Inches)
2
2.067
2- 1/2
2.469
3
3.068
4
4.026
3.6.1
Gas Supply Piping by Installer
The boiler and all gas piping connections should be pressure tested and must be checked for leaks before being
placed into service. Test with compressed air or inert gas if possible.
The boiler must be disconnected at the boiler manual shut-off valve (located at the end of the supplied gas train)
from the gas supply piping system during any pressure testing of the system at pressures in excess of 1/2 psig (14"
W.C.).
During any pressure testing of the gas supply piping system at pressures equal to or less than 1/2 psig (14" W.C.), the
boiler should be isolated from the gas supply piping system by closing the manual shut-off.
Some leak test solutions, including soap and water, may cause corrosion. These solutions should be rinsed off with
water after testing.
Boiler Main Gas
Valve
Union
Equivalent Pipe Length
90º Ell
Tee
(Feet)
(Feet)
5.17
10.3
6.16
12.3
7.67
15.3
10.1
20.2
Maximum Capacity in Cubic Feet of Natural Gas per Hour
Pressure Drop of 0.5 inch Water Column/Equivalent Length of Pipe
20
40
60
2750
1900
1520
4350
3000
2400
7700
5300
4300
15800
10900
8800
30
®
MACH
Gas Fired Boiler
(in feet)
80
100
150
1300
1150
950
2050
1850
1500
3700
3250
2650
7500
6700
5500
200
800
1280
2280
4600

Advertisement

Table of Contents
loading

This manual is also suitable for:

C2000hC2500C3000C4000

Table of Contents