Emergency Shut-Off; Typical Boiler Operating Conditions - Harsco Industrial C1500H Installation & Owner's Manual

Gas fired boiler natural gas/propane/dual fuel
Hide thumbs Also See for C1500H:
Table of Contents

Advertisement

4.3
E
S
MERGENCY
HUT
the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
AVERTISSEMENT! En cas de surchauffe ou si l'admission de gaz ne peut être coupée, ne pas couper ni débrancher
l'alimentation électrique de la pompe. Fermer plutôt le robinet d'admission de gaz à l'extérieur de l'appareil.
NOTICE! Manual gas shut off valves will be located either on the top of the boiler or on the back of the boiler
depending on your model boiler.
4.4
T
B
O
YPICAL
OILER
Model
Input
Number
Rating
(BTU/Hr)
C1500H
1,500,000
C2000H
2,000,000
C2500
2,500,000
C3000
3,000,000
C4000
4,000,000
NOTICE! The heat exchanger is constructed and stamped for 125 psig maximum operating pressure and 220ºF
maximum temperatures. The maximum setpoint is 185ºF.
-O
FF
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect
C
PERATING
ONDITIONS
Voltage
Total
Amperage
120/1/60
Less than 15
120/1/60
Less than 15
120/1/60
Less than 17
208-
Less than 20
240/3/60
480/3/60
Less than 20
208-
Less than 20
240/3/60
480/3/60
Less than 20
Manual gas
shut off
valve
Gas Flow Rate (CFH)
Natural Gas
1030
Btu/cu. ft.
1456
1942
2427
2913
3689
46
®
MACH
Gas Fired Boiler
LP Gas
Output Capacity
(Btu/hr)
2500
Btu/cu. ft.
600
1,440,000
800
1,920,000
1000
2,375,000
1200
2,850,000
1520
3,800,000