Table 2-6 Physical and Environmental Specifications for the Data Center Server
100-127
VAC
Watts
Minimum
363 W
Config.
Maximum
782 W
Config.
Typical
483 W
Config.
ASHRAE
Airflow cooling scheme (front to rear)
Class 1
1
Derate maximum dry bulb temperature 1 degree / 300 meters above 900 meters.
Table 2-7 (page 41)
server.
40
Server Specifications
Condition
Typical Heat
Nominal
Release
Airflow
200-240
VAC
Watts
CFM
m3/hr
363 W
61
104
782 W
79
134
483 W
61
104
shows the physical and environmental specifications for the Office Friendly
Weight
Maximum
Airflow @
35 degrees
1
Server
Rack
C
CFM
m3/hr
21 kg -
25 kg
28 kg (46
- 32
112
190
lb - 61
kg
lb)
(55
lb -
112
190
70
lb)
112
190
Min
Two 4 GB DDR2 DIMMs, n o PCIe/PCI-X public cards
config
or, RAID card on private I/O slot.
Max
Eight 4 GB DDR2 DIMMs, three PCIe/PCI-X cards on
Config
public I/O slots, and RAID card in private slot.
T ypical
Four 4 GB DDR2 DIMMs, one PCIe/PCI-X card on
Config
public I/O slots, and RAID card in private slot.
Server Dimensions
Pedestal
Rack
Pedestal
30 kg -
D 67.3
D 69 cm W 27.6
37 kg
cm W
cm (with feet) W
(66 lb -
48.3 cm
12.7 cm (w/o
81 lb)
H 8.6 cm
feet) H 50.8 (D
(D 26.5
27.2 in W 10.8 in
in W 19
(with feet) W 5.0
in H 3.4
in (w/o feet) H
in)
20.0 in)