Power Consumption And Cooling; Physical And Environmental Specifications - HP Integrity rx2800 - i2 User's & Service Manual

Rx2800 i2 user service guide
Hide thumbs Also See for Integrity rx2800 - i2:
Table of Contents

Advertisement

Power consumption and cooling

The power consumptions listed in
1.46 GHz quad-core CPU, 4 GB of memory, one 1200 W power supply, one SAS disk drive,
and one SATA DVD+RW drive).
All information in this section is based on primary power consumptions with one power supply
installed.
Table 12 Additional component power consumption
Processor
SAS disk drive (with I/O access)
SAS disk (idle)
PCIe card

Physical and environmental specifications

This section provides the temperature and humidity requirements, noise emission, and air flow
specifications for the server.
Operating temperature and humidity ranges may vary depending on the installed mass storage
devices. High humidity levels can cause improper disk operation. Low humidity levels can aggravate
static electricity problems and cause excessive wear of the disk surface.
Temperature, humidity, and sound power levels are provided in
NOTE:
De-rate maximum dry bulb temperature 1 degree/300 meters (1000 feet) above 900
meters 3000 feet).
Table 13 Environmental specifications (system processing unit with hard disk)
Operating temperature (up to 1524 m/5000 ft)
Non-operating temperature
Over-temperature shutdown
Operating humidity
Non-operating humidity
Sound Power Level
Sound Pressure Level
Altitude
Operating altitude
Non-operating altitude
24
Server Specifications
Table 12
Additional Component
Parameter
Acoustic Noise Emission (ISO 9296)
Maximum configuration (disk active)
are valid for a standard configuration as shipped (one
130 W
23 W
16 W
10 to 25 W
Data Center Server
1
+5° C to +35° C (+41° F to +95° F)
- 40° C to +70° C (5° F to 35° F)
+38 degrees; C (+100 degrees; F)
15% to 80% RH non-condensing
8% to 85% non-condensing
2
LwAd = 7.0 B
LpAm = 52.7 dB
0 to 3000 meters (10,000 ft.) maximum 0 to 3000
meters (10,000 ft.) maximum
0 to 4,600 m (15,000 ft.) maximum
Power Consumption
443.6 Btu/h
78.4 Btu/h
54.5 Btu/h
34.12 Btu/h to 85.30 Btu/h
Table
13.
Value
Office Friendly Server
LwAd = 6.0 B
LpAm = 42.4 dB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents