Setting Parameters

5-5
The following explains how to set the parameters.
Press and hold the
key in operation mode, or manual mode.
1
This switches you to the monitor mode Mv1.
Press and hold the
key in monitor mode
2
This switches you to the channel menu of setup mode.
Choose the channel with the
3
This switches you to the parameter menu.
Choose the parameter with the
4
The set value flickers.
Choose the parameter with the
5
The set value is fixed.
No matter where you are in monitor or setup mode, pressing the
operation mode. When setting the parameters in manual mode, pressing the key holds
manual mode and returns you to operation mode.
5-6

Key Lock and Password

Setting Key Lock
When key lock is activated, parameters cannot be changed but can displayed. Use the follow-
ing steps to set key lock.
Display the operation menu ("
1
Display key lock ("
LoC
") and press the
2
Set the value.
3
0 : No lock (all parameters can be changed. Initial value.)
1 : All lock (no parameters can be changed.)
2 : All lock without SV (only the SV can be changed.)
Press the
key to set the value.
4
Saving and entering a password
Use the following steps to save a password.
Display the password menu ("
1
Display password 1 ("
PAS1
") and press the
2
Set the password.
3
You can enter the hexadecimal value 0000 through FFFF.
Press the
key to set the value.
4
"
PAS2
" and "
PAS3
" can be saved in the same way.
The authority of the passwords grows from "
ity, the greater number of channels for display and settings.
Use the following steps to enter a password.
In monitoring mode, display ("
1
Enter a saved password and press the
2
You will be able to operate the equipment depending on the authority of your password.
Each parameter channel and the authority of passwords 1 to 3
Point
oPE ch
Pid ch
PLT ch
PrG ch
PAS1 permissions
<"PASS" = "PAS1">
Password
PAS2 permissions <"PASS" = "PAS2">
level
PAS3 permissions <"PASS" = "PAS3">
Note: When "
FEFE
" (FEFE) is entered as "
"DSP ch" can be displayed and set. This "super password" function is useful when
you forget the set passwords.
keys, then press and hold the
keys, then press the
key.
keys, then press the
key.
key returns you to
oPE Ch 1
").
key.
PAS Ch11
").
key.
PAS1
" to "
PAS2
" to "
PAS3
". The higher the author-
PASS
") and press the
key.
key.
Mon ch
SET ch
SyS ch
ALM ch
CoM ch
PFb ch
PASS
" (PASS), all of the channels "OPE ch" to
6

Parameter List

The following explains each channel parameter.
The list also shows the operational range of set values for parameters that are limited.
When the PV input lower limit (Pvb), PV input upper limit (PvF), or decimal place position
(Pvd) is changed, reconfigure all the initial parameter setting values.
When the parameter that has
once, and then re-start the controller.
key.
6-1
The following is a menu to operate the controller. Switchover between auto and manual control
output, switchover between RUN and standby, and other such functions.
Parameter
display symbol
man
"
" (MAn)
"
STbY
" (STby) Switchover
rEm
"
" (rEM)
PrG
"
" (PrG)
At
"
" (AT)
LA[h
"
"
(LACh)
Svn
"
" (Svn)
"
PLn1
" (PLn1) Currently
AL1
"
" (AL1)
"
AL1L
" (AL1L)
AL1h
"
" (AL1h)
"
AL5
" (AL5)
AL5L
"
" (AL5L)
"
AL5h
" (AL5h)
"
LoC
" (LoC)
PAS ch
dSP ch
6-2
Sets parameters for controls such as PID.
Parameter
display symbol
P
"
" (P)
i
"
" (i)
"
d
" (d)
hyS
"
" (hyS)
"
[oL
" (CoL)
– 6 –
RST
on its Remarks column is changed, turn off the power

Operation (Ch1)

Parameter name
Function
Switchover
Switchover between
between auto and
auto and manual
manual mode
modes
Switchover the
between RUN
operation mode
and standby
between RUN and
standby
Switchover
Switchover between
between local
local and remote SV
and remote SV
operation
operation
Ramp soak
Changes ramp soak
control command
run states
Auto-tuning run
Runs auto-tuning.
command
DO output latch
Cancels the DO
release command
latch state
Currently
Choose the SV No.
selected SV No.
used for control
Choose the PID
selected PID No.
group No. used for
control
AL1 set value
Set the alarm value. 0 to 100% FS
AL1L set value
AL1h set value
AL5 set value
AL5L set value
AL5h set value
Key lock
Sets the key lock to
prevent wrong
operation
PID (Ch2)
Parameter name
Function
Proportional band
Sets the
proportional band
of the PID
parameter. Setting
"0.0" will turn it to
an ON/OFF control.
Integration time
Sets the integration
time of the PID
parameter. Setting
"0" will turn off
integration.
Differential time
Sets the differential
time of the PID
parameter. Setting
"0.0" will turn off
derivation.
ON/OFF control
Sets the hysteresis
hysteresis
width for the ON/
OFF control.
Cooling
Sets the cooling
proportional band
proportional band
coefficient
coefficient. Setting
"0.0" will turn the
cooling into an ON/
OFF control.
Setting range
Initial
Remarks
value
oFF (auto) / on
oFF
(manual)
oFF (RUN) / on
oFF
(standby)
LoCL (local) / rEM
LoCL

(Note1)

(remote)
oFF (stop)
oFF
Displays End
rUn (run)
(when ending)
hLd (hold)
or GS (during
guaranty soak).
oFF (stop/finish)
oFF
on (normal type)
Lo (low PV type)
oFF / rST
oFF
(Note2)
(latch resets)
Sv0
Sv0
(Note20)
Sv1
Sv2
Sv3
Sv4
Sv5
Sv6
Sv7
di (chooses SV
according to di)
Pid 0 (PID ch)
Pid0
id
P
1
(PID group No. 1)
id
P
2
(PID group No. 2)
id
P
3
(PID group No. 3)
id
P
4
(PID group No. 4)
id
P
5
(PID group No. 5)
id
P
6
(PID group No. 6)
id
P
7
(PID group No. 7)
di (chooses PID
group according to di)
10°C
(Note3)
(absolute value
alarm)
-100 to 100% FS
(deviation alarm)
0 (no lock)
0
1 (all lock)
2 (All but SV locked)
Initial
Setting range
Remarks
value
0.0 to 999.9%
5.0%
0 to 3200 sec
240 sec
0.0 to 999.9 sec
60.0 sec
0 to 50% FS
1°C
0.0 to 100.0
1.0
(Note4)