Monitor (Ch5); Setup (Ch6); System (Ch7) - Fuji Electric PXG5 Instruction Manual

Micro controller x
Hide thumbs Also See for PXG5:
Table of Contents

Advertisement

Monitor (Ch5)

6-5
You can check the ramp soak progress, control output, heater current, remaining time, and
other status functions.
Parameter
Parameter name
Function
display symbol
StAt
"
" (STAT)
Ramp soak
Displays the
progress
progress of the
ramp soak
Mv1
"
" (Mv1)
MV1
Displays the output
value of the control
output (OUT1)
Mv2
"
" (Mv2)
MV2
Displays the output
value of the control
output
(OUT2)(during dual
control)
PFb
"
" (PFb)
Displays the PFB
Displays the input
input value
value of the
position feedback
rSv
"
" (rSv)
RSV input value
Displays the input
display
value of the RSV
(CT1)
" [t1"
Heater current 1
Displays the current
through the CT
(LC1)
"
LC1
"
Leak current value
Displays the leak
1
current value of CT.
(TM1)
" tm1"
Remaining time on
Displays the remaining
timer 1
time on timer 1
(TM5)
" tm5"
Remaining time on
Displays the remaining
timer 5
time on timer 5
" FALT"
(FALT)
Error source
Displays the
display
source of an error
" PLno
"( PLno)
Current palette No. Displays the PID
palette No.
currently selected.
" PTno
"( PTno)
Current pattern
Displays the
No.
pattern No. of the
ramp soak
currently selected.
6-6

Setup (Ch6)

Sets up the input range, output range, and other items for the equipment.
Parameter
Parameter name
Function
display symbol
"
PvT
" (PvT)
PV input type
Sets the type
of input sensor
Pvb
"
" (Pvb)
PV input lower
Sets the lower
limit
limit of PV input
"
PvF
" (PvF)
PVinput upper
Sets the upper
limit
limit of PV input
Pvd
"
" (Pvd)
Decimal point
Sets the number
position
of decimal point
positions for the
PV/SV
PvoF
"
" (PvoF)
PV input shift
Sets the amount
of shift for PV
input
tF
"
" (TF)
PV input filter
Sets the time
constant for the
PV input filter
"
rEm0
" (rEM0)
RSV Zero
Adjusts the zero
adjustment
RSV input
rEmS
"
" (rEMS)
RSV Span
Adjusts the
adjustment
span RSV input
"
rEmr
" (rEMr)
RSV input
Sets the range
range
for RSV input
"
rtF
" (rTF)
RSV input
Sets the time
filter
constant for the
RSV input filter
Setting range
Remarks
oFF (ramp soak stopped)
1-rP (ramp in step 1)
1-Sk (soak in step 1)
16rP (ramp in step 16)
16Sk (soak in step 16)
End (ramp soak finished)
-3.0 to 103.0%
-3.0 to 103.0%
(Note4)
-3.0 to 103.0%
(Note8)
-5 to 105% FS
(Note1)
0, 0.4 to 50.0A
(Note10)
(Note13)
0, 0.4 to 50.0A
(Note 10)
(Note 13)
0 to 9999 sec/ 0 to 9999min (Note3)
0 to 9999 sec/ 0 to 9999min
0bit: PFB input underflow
1bit: PFB input overflow
fixed at 0
8bit : PV input underflow
9bit : PV input overflow
10bit: underrange
11bit: overrange
12bit: RSV underrange
13bit: RSV overrange
14bit: range setting error
15bit: EEPROM error
0 to 7
0 to 6
Initial
Setting range
value
0 (no function)
3 (K)
1 (PT 100 Ω )
2 (J)
3 (K)
4 (R)
5 (B)
6 (S)
7 (T)
8 (E)
9 (no function)
10(no function)
11 (no function)
12 (N)
13 (PL-
)
2
14 (no function)
15 (0 to 5V / 0 to 20mA)
16 (1 to 5V / 4 to 20mA)
17 (0 to 10V)
18 (2 to 10V)
19 (0 to 100mV)
°
-1999 to 9999
0
C
°
-1999 to 9999
400
C
0 (No digit after decimal point)
0
1 (1 digit after decimal point)
2 (2 digit after decimal point)
-10 to 10% FS
0%FS
0.0 to 120.0 sec
5.0 sec
-50 to 50% FS
0%FS
-50 to 50% FS
0%FS
0-5 (0 to 5V)
1-5
1-5 (1 to 5V)
0.0 to 120.0 sec
0.0 sec (Note1)
Parameter
Parameter name
display symbol
[1r
"
" (C1r)
OUT1 range
[2r
"
" (C2r)
OUT2 range
FLo1
"
" (FLo1)
Output 1 set
value during
FALT
"
Flo2
" (FLo2)
Output 2 set
value during
FALT
"
SFo1
" (SFo1)
Soft Start
output 1 set
value
SFtm
"
" (SFTM)
Soft Start set
time
"
Sbo1
" (Sbo1)
OUT1 output
set value
during standby
" Sbo2"
OUT2 output
(
Sbo2)
set value
during standby
"
Sbmd
" (SbMd)
Standby mode
setting
"
Aot
" (AoT)
Types of AO
output
Remarks
"
AoL
" (AoL)
AO lower limit
scaling
RST
Aoh
"
" (Aoh)
AO upper limit
scaling
6-7

System (Ch7)

Assigns the functions of the DI/DO, LED lamp, and other controls.
Parameter
Parameter
display symbol
name
UkEy
"
" (UkEy)
Assigns the
USER key
RST
RST
RST
(Note1)
(Note1)
(Note1)
– 8 –
Function
Setting range
Sets the range
0-5 (0 to 5V)
of the control
1-5 (1 to 5V)
output (OUT1)
0-10 (0 to 10V)
2-10 (2 to 10V)
0-20 (0 to 20mA)
4-20 (4 to 20mA)
Sets the range
0-5 (0 to 5V)
of the control
1-5 (1 to 5V)
output (OUT2)
0-10 (0 to 10V)
(Also sets for the
2-10 (2 to 10V)
re-transmission
0-20 (0 to 20mA)
output)
4-20 (4 to 20mA)
Sets the output
-3.0 to 103.0%
value for the
control output
(OUT1) during
FALT
Sets the output
-3.0 to 103.0%
value for the
control output
(OUT2) during
FALT
Sets the output
-3.0 to 103.0%
value for the
control output
(OUT1) during
soft start
Sets the time from
00:00 to 99:59 (hour:min)
startup to the finish
of soft start
Sets the output
-3.0 to 103.0%
value for the
control output
(OUT1) during
standby
Sets the output
-3.0 to 103.0%
value for the
control output
(OUT2) during
standby
Sets the alarm
ALM
Ao
PV/SV
output, re-
display/
outpu
displa
transmission
output
t
y
output, and
0 OFF
ON
ON
PV/SV display
1 ON
ON
ON
during standby
2 OFF
OFF
ON
3 ON
OFF
ON
4 OFF
ON
OFF
5 ON
ON
OFF
6 OFF
OFF
OFF
7 ON
OFF
OFF
Displays the
PV
types of re-
SV
transmission
MV
output
DV
Sets the lower
-100 to 100%
limit of AO
Sets the upper
-100 to 100%
limit of AO
Function
Setting range
Sets the
0 (no function)
function of the
1 (Switchover between STBY ON/OFF)
[USER] key
2 (Switchover between Auto/Manual)
3 (Switchover between Local/Remote)
4 (no function)
5 (Starts AT (standard))
6 (Starts AT (low PV))
7 (Ramp SV on/off)
8 (Ramp SV HOLD)
9 (Ramp soak OFF)
10 (Ramp soak RUN/HOLD)
11 (no function)
12 (Latch release (all))
13 (Latch release (DO1))
14 (Latch release (DO2))
15 (Latch release (DO3))
16 (Latch release (DO4))
17 (Latch release (DO5))
18 (Start timer (DO1))
19 (Start timer (DO2))
20 (Start timer (DO3))
21 (Start timer (DO4))
22 (Start timer (DO5))
23 (SV No. + 1 (send))
24 (PID No. + 1 (send))
25 (no function)
mp soak
26 (Ra
pattern No.
+ 1 (send))
27 (SV No. + 1,
PID No. + 1 (send))
Initial
Remarks
value
0-10
(Note9)
(voltage
(Note14)
) 4-20
(current)
0-10
(Note12)
(voltage
(Note14)
) 4-20
(Note18)
(current)
-3.0%
-3.0%
(Note4)
103.0%
0.00
Be
(hour:
sure to
min)
set
0.00
during
dual
control.
-3.0%
-3.0%
(Note4)
0
(Note15)
RST
Pv
(Note12)
0%
(Note12)
100%
(Note12)
Initial
Remarks
value
2
RST