Ramp Soak (Ch4); Pid Palette (Ch3) - Fuji Electric PXG5 Instruction Manual

Micro controller x
Hide thumbs Also See for PXG5:
Table of Contents

Advertisement

Parameter
Parameter name
Function
display symbol
db
"
" (db)
Dead band
Shifts the cooling
proportional band
from the set value
bAL
"
" (bAL)
Output
Offset value which
convergence value
is added to the MV
output value
"
Ar
" (Ar)
Anti-reset
Sets the range of
windup
integration control
rEv
"
" (rEv)
Sets normal/
Sets the control
reverse operations
action
SvL
"
" (SvL)
SV limit
Sets the lower limit
(lower limit)
of SV
"
Svh
" (Svh)
SV limit
Sets the upper
(upper limit)
limit of SV
t[1
"
" (TC1)
OUT1 proportion
Sets the proportion
cycle
cycle of the control
output (OUT1)
(contacts, SSR drive)
t[2
"
" (TC2)
OUT2 proportion
Sets the proportion
cycle
cycle of the control
output (OUT2)
(contacts, SSR drive)
Plc1
"
" (PLC1)
OUT1 lower limit
Sets the lower limit
of the control output
(OUT1)
Ph[1
"
" (PhC1)
OUT1 upper limit
Sets the upper limit
of the control output
(OUT1)
"
PL[2
" (PLC2)
OUT2 lower limit
Sets the lower limit
of the control output
(OUT2)
Ph[2
"
" (PhC2)
OUT2 upper limit
Sets the upper limit
of the control output
(OUT2)
P[UT
"
" (PCUT)
Selects the type of
Sets the type of
output limiter
output limiter
6-3

PID Palette (Ch3)

Saves the palette values of PV and PID. Up to seven sets can be saved.
Parameter
Parameter name
Function
display symbol
Sv1
"
" (Sv1)
SV 1
Sets the SV set
value
P1
"
" (P1)
Proportional band 1
Sets the
proportional band
"
i1
" (i1)
Integration time 1
Sets the
integration time
d1
"
" (d1)
Differential time 1
Sets the
differential time.
hyS1
"
" (hyS1)
ON/OFF control
Sets the hysteresis
hysteresis 1
when using the
ON/OFF control.
[oL1
"
" (CoL1)
Cooling proportional
Sets the cooling
band 1
proportional band
"
db1
" (db1)
Dead band 1
Sets the dead
band
bAL1
"
" (bAL1)
Output convergence
Offset value which
value 1
is added to the
control output
"
Ar1
" (Ar1)
Anti-reset windup 1
Sets the anti-reset
windup
rEv1
"
" (rEv1)
Sets normal/
Sets the control
reverse 1
action
Sv7
"
" (Sv7)
SV 7
Sets the SV set
value
P7
"
" (P7)
Proportional band 7
Sets the
proportional band
"
i7
" (i7)
Integration time 7
Sets the
integration time
d7
"
" (d7)
Differential time 7
Sets the
differential time.
hyS7
"
" (hyS7)
ON/OFF control
Sets the hysteresis
hysteresis 7
when using the
ON/OFF control.
[oL7
"
" (CoL7)
Cooling proportional
Sets the cooling
band 7
proportional band
Initial
Setting range
Remarks
value
-50 to 50%
0%
(Note4)
-100 to 100%
0/50
(single/
dual)
0 to 100% FS
100%FS
rv-- (heat (reverse)
rv--/rvno
RST
/cool (none))
(single/
no-- (heat (normal)
dual)
/cool (none))
rvno (heat (reverse)
/cool (normal))
norv (heat (normal)
/cool (reverse))
rvrv (heat (reverse)
/cool (reverse))
nono (heat (normal)
/cool (normal))
0 to 100% FS
0% FS
(Note5)
0 to 100% FS
100% FS
(Note5)
1 to 150 sec
30:
(Note7)
Contact
2: SSR
drive
1 to 150 sec
30:
(Note4)
Contact
2: SSR
drive
-3.0 to 103.0%
-3.0%
-3.0 to 103.0%
103.0%
-3.0 to 103.0%
-3.0%
(Note4)
-3.0 to 103.0%
103.0%
(Note4)
0 to 15
0
Initial
Setting range
Remarks
value.
SV limit (lower)
0%FS
(Note5)
(SVL) to
SV limit (upper)
(SVH) %FS
0.0 to 999.9%
5.0%
0 to 3200 sec
240 sec
0.0 to 999.9 sec
60.0 sec
0 to 50% FS
1 °C
0.0 to 100.0
1.0
(Note4)
-50.0 to 50.0%
0%
(Note4)
-100.0 to 100.0%
0/50
(single/
dual)
0 to 100% FS
100%FS
rv-- (heat (reverse)/
rv--/rvno
(Note6)
cool (none))
(single/
RST
no-- (heat (normal)/
dual)
cool (none))
rvno (heat (reverse)/
cool (normal))
norv (heat (normal)/
cool (reverse))
rvrv (heat (reverse)/
cool (reverse))
nono (heat (normal)/
cool (normal))
SV limit (lower)
0%FS
(Note5)
(SVL) to
SV limit (upper)
(SVH) %FS
0.0 to 999.9%
5.0%
0 to 3200 sec
240 sec
0.0 to 999.9 sec
60.0 sec
0 to 50% FS
1 °C
0.0 to 100.0
1.0
(Note4)
– 7 –
Parameter
Parameter name
Function
display symbol
db7
"
" (db7)
Dead band 7
Sets the dead
band
"
bAL7
" (bAL7)
Output convergence
Offset value which
value 7
is added to the
control output
"
Ar7
" (Ar7)
Anti-reset windup 7
Sets the anti-reset
windup
"
rEv7
" (rEv7)
Sets normal/reverse
Sets the control
7
action
"
SvMX
" (SvMX)
Sets the Max SV
Choosing SV with
selection number
the user key sets it
to the maximum
possible number.
"
PL1m
" (PL1M)
Set the Max PID
Choosing PID with
selection number
the user key sets it
to the maximum
possible number.
6-4

Ramp soak (Ch4)

Create a pattern of temperatures using ramp soak combinations. You can create a temperature
pattern with up to 16 steps.
Parameter
Parameter name
Function
display symbol
"
Ptn
" (PTn)
Ramp soak
Sets which
operation pattern
steps to use in
(Step No.)
the ramp soak
operation
pattern
TiMU
"
" (TiMU)
Ramp soak time
Sets the units
units
of the ramp
soak time
Sv-1
"
"
Ramp soak 1 seg/
Sets the SV
(Sv-1)
SV
tm1r
"
" (TM1r)
Ramp soak 1 seg
Sets the ramp
ramp time
time
"
tm1S
" (TM1S)
Ramp soak 1 seg
Sets the soak
soak time
time
Sv16
"
"
Ramp soak 16 seg/
Sets the SV
(Sv16)
SV
"
t16r
"
Ramp soak 16
Sets the ramp
(T16r")
seg ramp time
time
t16S
"
" (T16S)
Ramp soak 16
Sets the soak
seg soak time
time
mod
"
" (Mod)
Ramp soak mode
Sets the
program
operation
method
"
Gsok
" (Gsok)
Guaranty soak
Sets the
ON/OFF
guaranty soak
ON or OFF
GS-L
"
"(GS-L)
Guaranty soak
Sets the lower
band (lower)
limit of guaranty
soak
GS-h
"
"(GS-h)
Guaranty soak
Sets the upper
band (upper)
limit of guaranty
soak
"PvST"(
PvST)
PV start
Sets whether or
not to start
ramp soak with
PV.
" ConT "(ConT)
Restore mode
Sets how to
restart when
the controller is
restored after a
power loss.
PTnM
"
" (PTnM)
Sets the Max
Choosing
pattern selection
pattern with the
user key sets it
to the
maximum
possible
number.
" PMin "(PMin)
Sets the Min
Choosing
pattern selection
pattern with the
user key sets it
to the minimum
possible
number.
Initial
Setting range
Remarks
value.
-50.0 to 50.0%
0%
(Note4)
-100.0 to 100.0%
0/50
(single/
dual)
0 to 100% FS
100% FS
rv-- (heat (reverse)
rv--/rvno
(Note6)
/cool (none))
(single/
RST
no--(heat (normal)
dual)
/cool (none))
rvno (heat (reverse)
/cool (normal))
norv (heat (normal)
/cool (reverse))
rvrv (heat (reverse)
/cool (reverse))
nono (heat (normal)
/cool (normal))
Sv0
Sv7
Sv1
Sv2
Sv3
Sv4
Sv5
Sv6
Sv7
di
Pid0
Pid
7
Pid1
Pid2
Pid3
Pid4
Pid5
Pid6
Pid7
di
Initial
Setting range
Remarks
value
0 (uses steps 1 to 4)
6
(Note 21)
1 (uses steps 5 to 8)
2 (uses steps 1 to 8)
3 (uses steps 9 to 12)
4 (uses steps 13 to 16)
5 (uses steps 9 to 16)
6 (uses steps 1 to 16)
di (according to di)
hh.MM (hour:min)
hh.MM
MM.SS (min:sec)
0 to 100% FS
0%FS
00.00 to 99.59 (hour:min/
00:00
min:sec)
(hour:min)
00.00 to 99.59 (hour:min/
00:00
min:sec)
(hour:min)
0 to 100% FS
0%FS
00.00 to 99.59 (hour:min/
00:00
min:sec)
(hour:min)
00.00 to 99.59 (hour:min/
00:00
min:sec)
(hour:min)
0 to 15
0
RST
oFF (guaranty soak off)
oFF
on (guaranty soak on)
0 to 50% FS
5°C
0 to 50% FS
5°C
oFF (PV start OFF)
oFF
on (PV start ON)
rES (Reset)
rES
(Note 20)
Con (Continue)
ini (Restart)
0 to 6,di
6
0 to 6, di
0