Model Specifications; Pxg5/9 Standard Model List; Timer Code; What Is Alarm With Hold? - Fuji Electric PXG5 Instruction Manual

Micro controller x
Hide thumbs Also See for PXG5:
Table of Contents

Advertisement

Dual Set Value Alarm Codes
Type
DO1 to DO5
Alarm Type
High/Low limit
16
High/Low absolute alarm
alarm
17
High/Low deviation alarm
18
High absolute/Low
deviation alarm
19
High deviation/Low
absolute alarm
20
High/Low absolute alarm
(with hold)
21
High/Low deviation alarm
(with hold)
22
High absolute/Low
deviation alarm (with hold)
23
High deviation/Low
absolute alarm (with hold)
Zone alarm
24
High/Low absolute alarm
25
High/Low deviation alarm
26
High absolute/Low
deviation alarm
27
High deviation/Low
absolute alarm
28
High/Low absolute alarm
(with hold)
29
High/Low deviation alarm
(with hold)
30
High absolute/Low
deviation alarm (with hold)
31
High deviation/Low
absolute alarm (with hold)

Timer Code

Type
DO1 to DO5
Alarm Type
Timer
32
ON delay timer
33
OFF delay timer
34
ON/OFF delay timer

What is alarm with hold?

Point
The alarm will not turn ON immediately when the process value gets into
the alarm band and enters again. If without hold, alarm may turn ON when
starting up.
power on
lower limit alarm
lower limit alarm
(with hold)
When alarm action code is changed, alarm set value may also become dif-
Caution
ferent from previous settings.
When alarm action type code is changed, turn off the power once, and
then re-start the controller, before starting control.
Aln: AL1 to AL5 show the alarm set values
ALnh: AL1h to AL5h show the alarm set values
ALnL: AL1L to AL5L show the alarm set values
dLYn: dLY1 to dLY5 show the alarm delay on set values
(Note1) Available only for DO2
* Other than the alarm setting, each of the event output functions can be assigned to
DO1 to 5.
For more details on each of the event output functions, refer to "7-12. Digital output" - "1. DO
event setting" (page 14).
Action diagram
PV
ALnh
ALnL
t
PV
ALnh
SV
ALnL
t
PV
ALnh
SV
ALnL
t
PV
ALnh
SV
ALnL
t
PV
ALnL
ALnL
t
PV
ALnh
SV
ALnL
t
PV
ALnh
SV
ALnL
t
PV
ALnh
SV
ALnL
t
PV
ALnh
ALnL
t
PV
ALnh
SV
ALnL
t
PV
ALnh
SV
ALnL
t
PV
ALnh
SV
ALnL
t
PV
ALnh
ALnL
t
PV
ALnh
SV
ALnL
t
PV
ALnh
SV
ALnL
t
PV
ALnh
SV
ALnL
t
Action diagram
DI
ALM
dLYn
DI
ALM
dLYn
DI
ALM
dLYn
dLYn
PV (process value)
Lower limit alarm
output area
power off
power on
on
on
off
off
off
on
off
off
12
Model Specifications
12-1

PXG5/9 Standard Model List

Digit Specifications
4
<Size of front WxH>
48 x 96 mm
96 x 96 mm
5
<Output 1>
Relay contacts
SSR drive
Current (0 to 20mA DC / 4 to 20mA DC)
Voltage (0 to 5V DC / 1 to 5V DC /
0 to 10V DC / 2 to 10V DC)
6
<Output 2>
None
Relay contacts
SSR drive
Current (0 to 20mA DC / 4 to 20mA DC)
Voltage (0 to 5V DC / 1 to 5V DC /
0 to 10V DC / 2 to 10V DC)
Re-transmission output current
(0 to 20mA DC/ 4 to 20mA DC)
Re-transmission output voltage
(0 to 5V DC / 1 to 5V DC /
0 to 10V DC / 2 to 10V DC)
Transmitter power supply
7
<Option 1>
None
RS 485
Digital input (No. 1) + digital input
(No. 2)
Digital input (No. 1) + RSV1
Digital input (No. 1) + CT1
RS 485 + digital input (No. 1)
RS 485 + RSV1
RS 485 + CT1
RS 485 + digital input (No. 1)+RSV1
Digital input (No. 1) + RSV1
+Digital input (No. 2)
8
<Revision symbols>
9
<Digital Output>
(Relay contact output)
None
Digital output 1 point (No.1)
Digital output 2 points (No.1, 2)
Digital output 3 points (No.1, 2, 3)
Digital output 2 points
[independent common] (No.1, 2)
10
<Power Supply> <Instruction Manual>
100V/240V AC no instruction
manual
100V/240V AC English instruction
manual
24V AC/DC no instruction manual
24V AC/DC English instruction
manual
11
<Option 2>
None
Digital input (No. 3, 4, 5) + CT2
Digital input (No. 3, 4, 5)
Digital input (No. 3, 4, 5)
+ digital outputs
(No. 4, 5) [transistor output]
Digital input (No. 3, 4, 5) + RSV2
12
13
Note 1: For outer dimensions of 48 x 96, the transmitter power supply output cannot be specified.
(5 in the fourth digit and T in the sixth digit cannot be specified.)
Note 2: If output 1 was for current or voltage output, option cannot be assigned to CT1 nor CT2.
(If 7th digit was assigned to G or J, or 11th digit to A, 5th digit cannot be assigned to E nor P.)
Note 3: RSV1 in option 1 and RSV2 in option 2 cannot be assigned simultaneously.
(If 7th digit was assigned to H or K, 11th digit cannot be assigned to D.)
Note 4: In case, in option 1, of DI 2 points + RSV1 or RS485 + DI 1 + RSV1, output 2 cannot be
assigned.
(If 7th digit was assigned to F or 2, 6th digit cannot be assigned to A, C, E, P, R nor S.)
Note 5: In case of CT1 in option 1, or CT2 in option 2, digit output cannot be assigned to None.
(If 7th digit was assigned to G or J, or 11th digit to A, 9th digit cannot be assigned to 0.)
Note 6: CT1 in option 1 and CT2 in option 2 cannot be assigned simultaneously.
(If 7th digit was assigned to G or J, 11th digit cannot be assigned to A.)
– 19 –
1 2 3 4 5 6 7 8 - 9 10 11 12 13 - 14 Notes
P X G 5
P X G 9
A
C
E
P
Y
A
C
E
P
R
S
T
Y
M
T
H
G
V
K
J
F
2
1
0
1
F
M
J
N
V
C
B
Y
A
B
C
D
0
Note 1
Note 2
Note 2
Note 4
Note 4
Note 4
Note 4
Note 4
Note 4
Note 1,4
Note 3
Note
2,5,6
Note 3
Note
2,5,6
Note 4
Note 4
Note 5
Note
2,5,6
Note 3
0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pxg9Micro controller x pxg5Micro controller x pxg9