Installation And Mounting; External/Panel Cut Dimensions; Installing Multiple Controllers; Installing Multiple Controllers Horizontally - Fuji Electric PXG5 Instruction Manual

Micro controller x
Hide thumbs Also See for PXG5:
Table of Contents

Advertisement

3

Installation and Mounting

3-1

External/Panel Cut Dimensions

PXG5
48
Waterproof packing
1-12
13-24
1
2
3
4
5
6
7
8
9
10
11
12
PC loader interface

Installing multiple controllers

+0.6
45
0
50 MIN.

Installing multiple controllers horizontally

(In this installing, the waterproof of PXG is lost.)
+0.8
(48 × n–3)
0
Panel cut dimensions should also meet the above dimensions after the panel
Caution
is coated.
Cautions when Close Fit Mounting:
When the power supply is AC 200V, keep the maximum ambient temperature
at 45°C. For vertical close-fit mounting, use a power source of AC 100V. (In
both cases, a fan is recommended as a measure against radiation.)
When there is an instrument larger than 70 mm or a wall to the right of
the controller, move it as least 30 mm away.
Cautions when wiring:
Start by wiring from the left-hand terminals (terminals 1 to 12).
Use a screw that is the right size on terminals and tighten them with a
torque of about 0.8 N/m.
Do not attach anything to unused terminals. (Do not use relay terminals.)
Mounting fixture
(fastening torque 0.15 N•m)
10
78
2
Panel thickness
t
1 to 8 mm
panel
25-36
terminal
screw M3
25
26
27
28
29
30
31
32
33
34
35
36
PXG9
96
waterproof packing
37-48
49-60
61-72
1-12
terminal screw M3
1
TOP
2
3
4
5
6
TOP
7
8
9
10
11
12
PC loader interface
Installing multiple controllers
+0.8
92
0
100 MIN.
– 3 –
mounting fixture
(fastening torque 0.15 N•m)
10
79.5
2
Panel thickness
t
1 to 8 mm
panel
13-24
25-36
25
26
27
28
29
30
31
32
33
34
35
36