This is called a delay function because there is a delay between the event and outputting to
DO.
(Ex.) Alarm On Delay
ON
Function
alarm
OFF
ON
normal
alarm relay
OFF
relay with
ON
ON delay
OFF
Use the following steps to set an alarm delay and hysteresis.
Display the alarm menu ("
ALM Ch 8
1
Display hysteresis 1 ("
A1hY
") and set the hysteresis.
2
Display delay time 1 ("
dLY1
") and set the delay.
3
Display delay time units 1 ("
4
Set the values for alarm 2 to alarm 5 as necessary.
5
Press the
key to set the value.
6
4. Setting the operation menu
Sets the alarm value so that DO is used as the alarm output.
Use the following steps to set this function.
Display the operation menu ("
1
Set the alarm 1 set value ("
AL1
2
The parameters displayed will vary according to the type of alarm.
Set up to alarm 5 as necessary.
3
Press the
key to set the value.
4
7-13

Communication Functions

Set the following to communicate with the host.
Display
Parameter
"
STno
"
ST No. setting
"
[oM
"
Parity/baud rate setting
"
S[[
"
Setting communication
permissions
Setting communication functions
Display the communication menu ("
1
Display ST No. setting parameter ("
2
ity/baud rate setting parameter ("
This sets the baud rate to 9600 bps and the parity to "even".
Display communication permissions ("
3
write permissions ("
rw
").
This sets the host to be allowed to read and overwrite the controller.
Press the
key to set the value.
4
Turn the controller off and on again.
5
The communication function settings will not be active until the power for the
Caution
controller is turned OFF/ON.
7-14
Re-transmission Output Function
The re-transmission output function delivers an analog output signal from the controller.
The following values can be output:
PV, SV, MV, DV (PV-SV), PFB
Depending on the type of output, you can choose the voltage type or current type.
The re-transmission output also contains a scaling function.
The following example shows a re-transmission output of 100% when PV=960°C (80% FS)
and a re-transmission output of 0% when PV=240°C (0% FS) for a PV range of 0 to 1200°C.
re-transmission output
calculation value
100°C
80% (AoH)
upper/lower limit
scaling range
20% (AoL)
0%
no relay output
cancel
ON delay
(alarm during delay is invalid)
set time
").
dL1U
") and set the units to minutes or seconds.
oPE Ch1
").
") or "
AL1L
" and "
AL1H
".
Function
Sets the station number.
Choose the configuration of parity and baud rate
Set whether or not the host has permission to
overwrite.
[oM [h 9
").
Stno
") and choose 1, and then display Par-
CoM
") and choose 9600 bps, even ("
S[[
") and choose to allow read and over-
actual re-transmission
output
100%
0%
Setting re-transmission output function
Display the setup menu ("
1
Display the AO output function parameter ("
2
This selects PV as the re-transmission output.
Display AO lower limit scaling ("
3
example, set it to 20%).
Display AO upper limit scaling ("
4
example, set it to 80%).
Press the
5
7-15
The remote SV function controls the analog input signal coming into the controller as SV .
The input terminal becomes RSV1 or RSV2.
The remote SV function contains a zero/span adjustment function, as well as an input filter
function.
The setup menu ("
function.
Display
"
rEMO
" (rEMO)
"
rEMS
" (rEMS)
rEMr
"
" (rEMr)
rTF
"
" (rTF)
Switching to remote SV operation
Display the operation menu ("
1
Display the switching to remote SV parameter ("
2
("
rEM
").
Press the
3
Caution
7-16
The heater wiring passes through the CT, allowing the current value to be monitored and
detect errors in the heater line.
Heater break are detected by drops in the heater current. Setting the detection values acti-
vates this function.
Related parameters: "
Refer to
For details on the heater break alarm, refer to the "Operation Manual".
7-17
96ev
").
Detects when the control loop is open (break) without using the CT , but instead observing the
control output and PV.
Related parameters: "
Refer to
For details on the loop break alarm, refer to the "Operation Manual".
7-18
The heater wiring passes through the CT, allowing the current value to be monitored and
detect errors in the heater line.
The load short-circuit is detected by drops in the heater current. Setting the detection values
activates this function.
Related parameters: "
Refer to
For more details on the load short-circuit alarm, refer to the "Operation Manual"..
7-19
1. Soft start function
When turning on the equipment (including the temperature controller), the soft start function
suppresses the MV to become maximum output. It places an upper limit on MV output for a
specified amount of time after power is turned on.
This function is useful for effects such as suppressing the heater output during equipment star-
tup, and makes load lightened.
After the specified time has passed after switching on the equipment (or if SFTM = 0), the soft
start function ends and normal controls begin.
– 15 –
SET [h 6
").
AoL
") and set the lower limit scaling (in this
AoH
") and set the upper limit scaling (in this
key to set the value.

Remote SV Function

") must be set in the following manner before using the remote SV
SET [h 6
Parameter
Function
RSV Zero adjustment
Adjusts the zero of the RSV input
RSV Span adjustment
Adjusts the span of the RSV input
RSV input range
Sets the range for RSV input
RSV input filter
Sets the time constant for the RSV input filter
PV
PID
local
calculation
SV
remote SV
(DC0 to 5/1 to 5V)
Switch to remote SV parameter rEM
oPE [h 1
").
key to set the value.
Soft start is not displayed during the remote SV operation.
Do not use remote SV and the SV selection function at the same time.

Heater Break Alarm Functions

hb1
", "
hb1h
" ("
ALM Ch 8
"), "
Ct1

Loop Break Alarm

LbTM
", "
TbAb
" ("
ALM Ch8
")
Load Short-circuit Alarm
hS1
", "
hS1h
" ("
ALM Ch8
")
Other Functions
Aot
") and choose the PV.
control output
") and choose remote
rEm
","
LC1
" ("
Mon Ch 5
")