• To measure the outdoor temperature as accurately as possible,
the sensor must be positioned 2/3 of the way up the facade on
houses up to three storeys high. For higher buildings, the sensor
should be positioned between the second and third storeys. Its
location must not be completely protected from the wind but
not in a direct draft. The outdoor sensor should not be placed on
reflective panel walls.
• The sensor must be positioned at least 1 m from openings in the
walls that emit hot air.
• If the sensor cable is connected through a pipe, the pipe must be
sealed so that the sensor is not affected by outgoing air.
Then connect the sensor to the heat pump control system in
accordance with the instructions below.
1. Route the outdoor sensor connection cable through the cable
bushing in the top panel to the terminal block.
2. Connect the sensor to the terminal blocks according to the con-
nection diagram.
6 .4
Changing the language in the control
computer
If necessary, change the language in the control computer menus.
1. Ensure that the main circuit breaker is on.
2. Open the SERVICE menu by pressing and for three sec-
onds.
3. Change language in the control computer menu SERVICE ->
INSTALLATION -> ENGLISH, select language and .
6 .5
Changing the number of auxiliary heat-
ing power stages
NOTE! Setting the maximum permitted number of power
stages for the auxiliary heating must be carried out.
1. Ensure that the main circuit breaker is on.
2. Open the SERVICE menu by pressing and for three sec-
onds.
3. Change the number of auxiliary heating power stages in the
control computer menu SERVICE -> ADD.HEAT -> MAXSTEP,
select the number of stages and
6 .6
Connecting the outdoor unit, DHP-A 6
and DHP-A 8
NOTE! The power cable may only be connected to the termi-
nal block intended for this purpose. No other terminal blocks
may be used!
For correct connection between the heat pump and the outdoor
unit, 6 connections must be made, see also separate sheet with
electrical connections.
Ground
0V
Phase high speed (575 rpm)
Phase low speed (340 rpm)
Motor protection fan
Figure 34: Connecting the outdoor unit .
1. Route the power cable through the opening in the top panel of
the heat pump to the terminal blocks.
2. Connect the power cable to the terminal block.
22
.
VMBMA102
6 .7
Connecting the outdoor unit, DHP-A 10
and DHP-A 12
NOTE! The power cable may only be connected to the termi-
nal block intended for this purpose. No other terminal blocks
may be used!
For correct connection between the heat pump and the outdoor
unit, 6 connections must be made, see also separate sheet with
electrical connections.
Ground
0V
Phase high speed (925 rpm)
Phase low speed (575 rpm)
Motor protection fan
Figure 35: Connecting the outdoor unit .
1. Route the power cable through the opening in the top panel of
the heat pump to the terminal blocks.
2. Connect the power cable to the terminal block.
6 .8
Connecting the defroster sensor, DHP-A
Figure 36: Connecting the defroster sensor .
Position the defroster sensor on the reverse of the outdoor unit.
1. Route the defroster sensor connection cable through the cable
bushing in the top panel to the terminal block.
2. Connect the sensor to the terminal blocks according to the con-
nection diagram.