Commissioning
5.2

Select display language

1. Press
in the upper left corner of the Start screen
2. Press
3. Press on the text Language.
4. Select language.
5. Press to return to System settings.
Or press
in the upper left corner to return to the Menu screen.
5.3

Setting date and time

1. Press
in the upper left corner of the Start screen.
2. Press
3. Press on the text System settings.
4. Press on the text Date/time.
5. Press + or – for each field to change the setting.
6. Press
to confirm settings.
7. Press to return to System settings.
Or press
in the upper left corner to return to the Menu screen.
5.4

Internal Immersion Heater

The heat pump is equipped with an electrical immersion heater.
The Immersion heater may, depending on settings, be used to:
▪ Perform anti-legionella top up heating
▪ Act as backup heater in the event of disabled heat pump
▪ Provide extra heating power, if needed, to fulfil the heating demand
The standard factory fitted immersion heater has 3 steps:
▪ Step 1: 3kW
▪ Step 2: 6kW (Default)
▪ Step 3: 9kW
The settings of permitted steps may be configured differently with and without compressor to suit individual demands.
NOTE: To ensure that the anti-legionella top up heating may be done, the minimum step without compressor is step 1.
Ensure that the main circuit breaker is on.
Danfoss Heating Solutions
DHP-H Varius Pro+/DHP-L Varius Pro+
1. Press
on the Start screen to open the Menu screen.
2. Press
3. Enter the code for installer access: 60,70,80.
4. Press on Settings
.
5. Press to go to the menu page for Internal immersion heater.
6. Press on the text Internal immersion heater.
7. Make the desired changes.
8. Confirm settings by pressing
VIJSG202
15