Monitoring temperatures
and system units - line B
Controlled units
1
1
2
B
ON
ON
ON
No. of active
I I
2
stages (II)
5
5
Flow temp.
(S3/S5*)
*
If sensor S3 is not connected, the sensor S5 values will be displayed
Push and hold the shift button to see:
- the calculated flow temperature
- the desired return temperature limitations.
The activity of the motorized control valve is shown as arrows
below the valve symbol. When the circulation pump is
operating, it is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display will
indicate it as "- -".
If the sensor is short-circuited, the display will indicate
it as "- - -".
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
Relationship between temperature and ohmic value
°C
1600
-50
805
1500
-40
845
-30
883
-20
922
1400
961
-10
1000
0
1300
10
1039
20
1078
30
1117
1200
40
1155
50
1194
1100
60
1232
1271
70
1000
1309
80
90
1347
100
1385
900
110
1423
120
1462
800
130
1501
140
1539
1578
150
-50
-25
The grey
side of the
ECL Card
2
3
ON
Max. no. of stages
0
25
50
75
100
125
150
Manual control -
line B
Shift to manual mode.
Choose the unit you want to control. The selected
unit symbol will blink.
Controlled units
when the relevant button is pushed.
Heat pump and electric heater are cut-in or -out
when the relevant button is pushed.
The motorized actuator (gear motor /
change-over valve)
closes
the relevant button is pushed. If pushed for more
than 3 seconds, the actuator continues to close or
open the valve.
The thermo actuator
activates
pushed. If pushed for more than 3 seconds, the
actuator continues to open the valve.
Check the activation direction of the actuator either by
looking at it or by feeling whether the temperature of the
actual pipe changes as expected.
This operation applies to both circuits, if available.
During manual operation, all control functions are deactivated.
°C
Controlled units
1
1
2
2
3
Controller mode
B
ON
ON
ON
ON
I I
2
5
5
1
are switched OFF or ON
ON ON
or opens
the controlled unit as long as
the valve as long as the
19
button is
The grey
side of the
ECL Card