Danfoss DHP-H Installation And Service Instructions Manual page 33

Danfoss heat pumps installation and service instructions
Table of Contents

Advertisement

HYSTERESIS
In order to start the heat in advance during sudden changes of the heat demand, there is a value, HYSTERESIS, which controls the differ-
ence between the actual supply temperature, t1 and the calculated supply temperature, t2. If the difference is the same or greater than the
set HYSTERESIS value (x), i.e. there is a heat demand, or the heat demand disappears, quicker than the usual integral calculation, the inte-
gral value is forced to either the start value INTEGRAL A1 or to the stop value 0°min.
SUPPLY TEMP.
INTEGRAL
HYSTERESIS
(∆t) ≥ x
Compressor start
(-60)
Figure 58: Conditions for HYSTERESIS to force the integral value to change .
t
1
t
2
HYSTERESIS
(∆t) ≥ x
Compressor stop
(0)
VMBMA102
TIME