Danfoss DHP-H Installation And Service Instructions Manual page 43

Danfoss heat pumps installation and service instructions
Table of Contents

Advertisement

Sub menu SERVICE -> INSTALLATION
Used for settings that are set during installation
Menu selection
SWEDISH
SYSTEM
NOTE! The menu selec-
tion in the SYSTEM menu
varies depending on the
selected values. Tip: start
in the top menu and
work downwards.
SERVICETIME
FACTORY SET
RESET OPERAT. TIME
CALIBRATION SENSOR
LOGTIME
Meaning
Language setting for the control computer.
Sub menu SERVICE -> INSTALLATION -> SYSTEM:
Menu selection
Meaning
HEAT SOURCE
GROUND OR ROCK
OUTSIDE AIR (Defrost card)
HEATING SYSTEM
VL-SYSTEM
D-SYSTEM
VLD-SYSTEM (appears if OUTSIDE AIR is selected)
COOLING
COOLING PASSIVE: OFF/EXTERNAL/INTEGRATED IN HP
(Expansion card)
COOLING ACTIVE: OFF/EXTERNAL
ROOM SENSOR: 0/1 (Appears if room sensor is installed)(0=controls to a constant
value, 1=controls to the value that the room sensor has)
POOL
ON/OFF
(Expansion card)
SHUNTGROUP
ON/OFF
(Expansion card)
When ON, HEAT CURVE 2 is activated in the INFORMATION menu.
ADD. HEAT
CONTROLLED CP: only OFF
FLOW SWITCH: ON/OFF
CURRENT LIMITER: ON/OFF(Expansion card)
PHASE FAULT: OFF / PHASE READING
-
NOTE! Only used for test operation. Simulates time 60 times as fast, which
means that the waiting times are eliminated during test operation.
0 = deactivates SERVICETIME
1 = activates SERVICETIME which speeds up the control computer's integral cal-
culation and start delay by 60 times.
0 = starting point, the value returns to zero after a change
R = reset factory settings for radiator system
G = rest factory settings for under floor heating
0 = no reset of operation times
1 = reset operation times to zero
Following sensors are in the installation:
OUTDOOR
SUPPLY PIPE
RETURN PIPE
HOT WATER
BRINE OUT
BRINE IN
DEFR SENSOR
EXTERNAL INFLUENCE (these parameters affect all sensors except the outdoor
sensor. The parameter compensates for the external influence on the sensor that
is mounted in the heat pump.
Time interval between collection points of temperature history in minutes. The
history graphs always show the 60 last collection points, which means that the
graphs can display history from 1 hour up to 60 hours ago.
(The function is not active if there is an active alarm).
VMBMA102
Factory setting
SWEDISH
(SVENSKA
NORSK,
SUOMI,
DEUTSCH,
NEDERLANDS,
ENGLISH,
FRANCAIS
POLSKI
EESTI
DANSK
ESPANOL
LATVIESU VALODA)
-
-
-
(interval: -5°C - 5°C)
0 (at OUTSIDE AIR 5)
(interval: 0 - 20)
1M (interval: 1M - 60M)
4