Danfoss DHP-H Installation And Service Instructions Manual page 39

Danfoss heat pumps installation and service instructions
Table of Contents

Advertisement

Sub menu INFORMATION -> TEMPERATURE
Used to indicate the prevailing temperatures, history and set/calculated values. History can be accessed to view all the values by pressing
the right arrow to present a graph of the last 100 measurement points for the set time interval (SERVICE -> INSTALLATION -> LOGTIME). In
the event of an alarm, history stops being logged until the alarm is reset by changing the operating mode to OFF.
Menu selection
OUTDOOR
ROOM
SUPPLY PIPE
RETURN PIPE
HOT WATER
INTEGRAL
BRINE OUT
BRINE IN
POOL
(Expansion card)
SHUNTGROUP
(Expansion card)
COOLING
(Expansion card)
CURRENT
(Expansion card)
Sub menu INFORMATION -> OPERAT . TIME
Used to show the operating time for each component. Time given in hours.
Menu selection
HEATPUMP
ADD. HEAT 1
ADD. HEAT 2
ADD.HEAT 3
(Defrost card)
HOT WATER
COOLING
(Expansion card)
COOLING ACTIVE
(Expansion card)
Sub menu INFORMATION -> DEFROSTING (DHP-A)
The menu applies to DHP-A with defroster card and only appears if OUTDOOR AIR in the SERVICE -> INSTALLATION -> SYSTEM -> HEAT
SOURCE menus is selected. Used to obtain information about outdoor unit defrosting and to make certain settings.
Menu selection
DEFROSTS
BETW. 2 DEFR
TIME SINCE DEFROST
FAN H OFF AT
DEFROST CURVE
MANUEL DEFR
Meaning
Shows the actual outdoor temperature.
Shows the actual set temperature.
Shows the actual supply temperature. The calculated supply temperature to the
house is within brackets.
Shows the actual return temperature. The stop temperature, MAX RETURN is
within brackets.
Shows the actual hot water temperature.
Shows the actual calculated value for integral.
Shows the actual temperature for the brine system's supply pipe.
Shows the actual temperature for the brine system's return pipe.
Only appears if POOL is selected. Shows the actual pool temperature. The set
pool temperature is shown in brackets.
Only appears if SHUNTGROUP is selected. Shows the actual supply temperature.
The calculated supply temperature to the shunt group is within brackets.
Only appears if COOLING is selected. Shows the actual supply temperature. The
set point value is shown in brackets.
Only appears if CURRENT LIMITER is selected. Shows the actual current con-
sumption. The set value for MAX CURRENT is shown between brackets.
Meaning
Compressor operating time for both heating and hot water production.
Operating time auxiliary heater power stage 1 with full output 3 kW (VL).
Operating time auxiliary heater power stage 2 with full output 6 kW (VL).
Operating time auxiliary heater power stage 3 with full output 6 kW (VL).
Operating time hot water with compressor.
Operating time passive cooling.
Operating time active cooling.
Meaning
Total number of defrosts carried out.
The operating time of the compressor in minutes between the 2 last defrosts.
The operating time of the compressor in minutes since last defrost.
Fan high speed is deactivated at this temperature and low speed is activated.
Here, the angle of the defrost curve can be changed using the right-hand arrow
and by either pressing + or – (Change the start temperature for defrost).
By using the right-hand arrow + or -, defrost can be started manually (shunts
+20°C for 10 minutes).
VMBMA102
Factory setting
-
-
-
-
-
-
-
-
-
-
-
-
Factory setting
-
-
-
-
-
-
-
Factory setting
-
-
-
-
-10°C (interval: -10°C
- -4°C)
-