fig. 50
Checking the condensate siphon
fig. 51
Checking the ignition electrode
59970LTGBW7H0234
3 to 4 mm
>1 min
59970LTGBW7H026
40
Remeha Avanta
3.1.2
Checking the condensate siphon
• Check the condensate siphon. Remove any dirt residues
and refill with clean water to the mark.
3.1.3
Checking the ignition electrode
• Check the ionisation /ignition electrode for:
- deposits (remove any white deposits with abrasive cloth);
- the adjustment of the ignition electrode (between 3 and 4
mm);
- the quality of the gasket and condition of the porcelain
(this should not be cracked);
• Check the ionisation current after 1 minute on the display
code fl, see par. 2.10.6.
If the read-out value is lower than 3 or higher than 9μA, check
cable and connections are sound if OK
replace the ignition electrode.
The ignition cap is fixed on the ignition electrode and therefore
cannot be removed.