Inspection And Maintenance; Inspection; Checking The Flue Pipes And Air Supply Pipes For Leaks - REMEHA Avanta 12v Installation & Service Manual

Avanta range
Table of Contents

Advertisement

3

INSPECTION AND MAINTENANCE

fig. 48
Annual inspection
fig. 49
Checking flue pipes
The Remeha Avanta is practically maintenance free but should
be inspected annually.
If during the annual inspection the flue gas analysis indicates
that the values are outside the figures given in table 09, main-
tenance work should be carried out as described in par.3.2.
Also carry out maintenance if the ionisation read-out value is
lower than 3 or higher than 9μA, or when the flame core is not
correct.
Only Remeha spare parts/materials should be used.
All service and maintenance must be carried out by a qualified
Engineer with the relevant training and certification (i.e. ACS
- IEE registrations etc).
3.1

Inspection

The annual inspection of the Remeha Avanta can be limited to
the following checks:
- check the flue pipes and air supply pipes for leaks, see par.
3.1.1.;
- check and clean (if necessary) the condensate siphon, see
par.3.1.2.;
- check the ignition electrode and ionisation, see par. 3.1.3;
- check the combustion and flame pattern, see par. 3.1.4;
- Fill in the Benchmark Service Record on the inside back
pages of this document.
59970LTGBW7H022
3.1.1
Checking the flue pipes and air supply pipes for
leaks
• Check that the flue and air-supply connections and pipes
are sealed and the terminal exit is clear.
59970LTGBW7H023