Error Read Outs; Deleting Errors - REMEHA Avanta 12v Installation & Service Manual

Avanta range
Table of Contents

Advertisement

R
fig. 61

Error read outs

4.4.1
Error read outs
• Press the [enter]-key and keep it pressed;
• Press the [reset]-key until codes c and 0 appear alter-
nately in the display;
• Enter the special access code 88 with the [+] or [-]- key;
• Press the [enter]-key; the display shows ér and the
number of the last error alternately, for example 02.
• Press the [+] or [-]-key to go forwards or backwards in the
list of errors.
• Press the [enter]-key to take a closer look ot the error. The
display shows the error code as follows;
- first error code é with error number e.g. 12
- then status code 5t with status number e.g. 3 (burning
for central heating)
- then number of time that the error has occurred ñ and a
number e.g. 3
- then the flow temperature when the error occurred t1
and temperature e.g. 75
- final the return temperature when the error occurred t2
and temperature e.g. 60
This cycle continues to repeat itself.
• Press the [reset]-key to stop the cycle; the following
appears in the display;
ér and e.g the numbers 1 and 8.
• Press the [+] or [-]-key to look at the following error data.
4.4.2

Deleting errors

The last message in the list, Er followed by cl will
appear in the display;
• Press the [enter]-key again, and the following will appear in
the display: 0
• Press the [+]-key to set the parameter to 1.
• Press the [enter]-key, to delete the error memory:
• Press the [escape]-key twice to exit the error memory.
When tracing an error, the cause can often be found more
quickly if the operating status at the time the error occurred
can be retrieved from the error memory.
LT.AL.W7H.000.064