3 Functions of NB-Designer
For example:
(1) For the User Permission Setting of User 0: Check the [Enabled] option and set the User
Name to Administrator, Password to 666666 and Logoff Time to 1 minute. Assign 4
Authorities, i.e. Operation Permission, Process Permission, System Config Permission and
Add/Delete User Permission respectively for the "Administrator (User 0)".
(2) For User Permission Setting of User 1: Check the [Enabled] tab and set the User Name to
Engineer, Password to 222222 and Logoff Time to 10 minutes. Assign 1 Authority, i.e.
Process Permission to the "Engineer (User 1)".
Besides the User Permission Setting in HMI Attribute, the following special registers are also
needed to create the editing project related to the user permission.
Addresses
LW9486~LW9501
LW9502~LW9503
LW9504~LW9505
LB9165
LB9166
2
Dynamically Add/Delete User Permission
The user can not only set the user permission in the software, but also perform online user
addition/deletion or permission addition/deletion in the HMI. The following special registers are
needed for creating the related editing project.
3-294
Functions
Input the login user name.
Input the password corresponding
to the login user.
Display the current user authority.
Confirm the user login conditions.
Confirm the user logoff conditions.
NB-series Programmable Terminals NB-Designer Operation Manual(V106)
Descriptions
32 characters max.
Double-word
Double-word, read-only component, the
corresponding 32 authorities.
After it is turned ON, the login operation is
performed, and later it is turned OFF automatically.
After it is turned ON, the logoff operation is
performed, and later it is turned OFF automatically.