Item
Input power supply voltage
Fuse (built-in,
irreplaceable)
Power consumption
With backlight off
Inrush current
Permissible instantaneous
power failure time
Noise immunity
Dielectric withstand voltage
Insulation resistance
Applicable wire size
Applicable solderless
terminal
Applicable tightening torque
(Terminal block terminal
screw)
Remark
3 - 9
3.4 Power Supply Specifications
GT1155-QTBDQ
GT1155-QTBDA
DC24V(+10% -15%)ripple voltage 200mV or less
1.0A
11.16W (465mA/24VDC) or
less
5.04W (210mA/24VDC) or less
26A or less (26.4V) 4ms
Within 10ms
Noise voltage: 500Vp-p, Noise width: 1
frequency)
500VAC for 1 minute (across power supply terminals and earth)
10M
or larger as measured with the 500 VDC insulation resistance tester (across
power supply terminals and earth)
0.75 to 2[mm
2
]
Solderless terminal for M3 screw RAV1.25-3, V2-N3A, FV2-N3A
0.5 to 0.8[N•m]
Operation at momentary power failure
The GOT continues to operate even when the instantaneous power failure occures
within the permissible instantaneous power failure time.
The GOT stops operating if there is extended power failure or voltage drop, while it
automatically resumes operation as soon as the power is restored.
Specifications
GT1155-QSBDQ
GT1155-QSBDA
9.72W (405mA/24VDC) or
less
s (by noise simulator of 25 to 60 Hz noise
GT1150-QLBDQ
GT1150-QLBDA
7.92W (330mA/24VDC) or
less