How To Connect Wiring To The Terminal; For Stranded Wiring; How To Set The External Static Pressure Of Each Type (Us Type); External Static Pressure - Sanyo SPW-C0705DZH8 Technical Data Manual

3-way eco-i multi system 5 series
Table of Contents

Advertisement

3. Electrical Wiring

How to connect wiring to the terminal

For stranded wiring

(1)
Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring about 10
mm and tightly twist the wire ends.
(2)
Using a Phillips head screwdriver, remove the ter-
minal screw(s) on the terminal plate.
(3)
Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure
terminal.
(4)
Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a screw-
driver.

How to set the External static pressure of each type (US Type)

The standard (before shipment) external static pressure is shown in the table below.
When using with a higher static pressure, it is necessary to change to the high static pressure mode.

External static pressure

Type
Standard
High static pressure
When using with high static pressure mode, set the indoor unit control board as shown below.
Follow the below procedure while the unit is turned off.
(1) Open the cover of the electrical box and confirm that it is the indoor unit control board.
(2) Connect the short circuit connector to the short circuit pin TP3 (2P: Yellow) of the indoor unit control board.
Wire
75
95
125
10
15
15
30
30
40
Indoor control board
2-29
Design of 3-WAY ECO-i SYSTEM
Stranded wire
Special
Screw
washer
Ring pressure
terminal
Terminal plate
Wire
165
185
15
15
40
40
White Yellow Red
TP6
TP3
TP1
Ring
pressure
terminal
Screw and
Special washer
Ring
pressure
terminal
1
2
3
4
5
6
7
8