Intaking Fresh Air Of Semi-Concealed Type And Concealed-Duct Type; Precautions Regarding External Air Intake; Arranging Ducts And Filters In The Field; Thermal Insulation For Ducts - Sanyo SPW-C0705DZH8 Technical Data Manual

3-way eco-i multi system 5 series
Table of Contents

Advertisement

13. Intaking Fresh Air of Semi-Concealed Type and Concealed-Duct Type

Precautions Regarding External Air Intake

(1) Ventilation Load
Ensure that the design of the air-conditioner takes air-conditioning loads into consideration when external air
intake is involved.
(2) Restrictions on External Air Intake
Ensure that the design conforms to the restrictions on air intake volume stipulated in accordance with the model
of the indoor unit and the intake method. Consideration must also be taken to mixed air content listed in (3)
below without fail.
* If the air intake volume does not satisfy the required ventilation volume, air must be fed into the room
separately with the use of a total heat exchanger or a fresh air processing air-conditioner, etc.
(3) Mixed Air
The amount of external air intake must be set within the scope of the unit's usage conditions when external air and
internal air is mixed together. This is especially important in the following cases, in which it is necessary to either
feed external air into the room after it has been processed or reduce the amount of external air that is fed in.
A
When the external dew-point temperature is greater than the dry-bulb temperature of the air sucked into the
unit.
Ensure that processing is performed so that the external dew-point temperature is lower than the temperature
of the air sucked into the unit to prevent the risk of condensation building up.
1
B
In the case of low external temperatures.
There are cases in which the temperature of mixed air is lower than the operating range of the unit if
excessive amounts of external air intake are used when the external temperature is low. This problem is to
be solved by either feeding external air into the room after it has been processed or reducing the amount of
external air that is fed in.
2
C
When used in combination with humidifi ers
External air must always be processed when the external air temperature reaches freezing point to prevent
the risk of the humidifi er freezing.
3

(4) Arranging Ducts and Filters in the Field

External air intake ducting must be arranged in the fi eld. External
air fi lters must also be installed without fail in order to prevent the
intake of dust and grit.

(5) Thermal Insulation for Ducts

4
Ensure that all external air intake ducting is heat-insulated
without fail. Failure to observe this may result in the build-up of
condensation.
(6) External Air Intake Coupling
Ensure that the design for external air intake is coupled with the
5
fan blower operations of the indoor unit. There are cases in which
the dust that accumulates in the fi lter is blown into the room if the
external air is fed from the fi lter. There are also cases in which
the noise of external air being fed into the room can be heard
from the indoor unit if external air is forcibly fed when the booster
6
fan or other components on the indoor unit are not operating.
(7) Booster Fan Selection
Select the booster fan in accordance with the resistance of
the external air intake duct (diagram on the pressure loss
7
characteristics of the air fl ow volume for fl exible cylindrical ducts)
and the resistance prevalent inside the unit (volume of external
air fed and the resistance within the unit).
(8) Attaching the External Air Intake Flange
8
3-WAY ECO-i SYSTEM Unit Specifi cations
o100
30
20
10
6
4
2
1
0.8
0.6
0.4
0.2
0.1
Air Flow Volume for Flexible Cylindrical
Duct-Pressure Loss
4-368
Flexible Cylindrical Duct
30
50
100
200 300
400
500
3
Airflow (m
/h)
o125

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Spw-c1405dzh8Spw-c0905dzh8Spw-c1305dzh8Spw-c1155dzh8

Table of Contents