Sanyo SPW-C0705DZH8 Technical Data Manual page 98

3-way eco-i multi system 5 series
Table of Contents

Advertisement

3. Timer Remote Controller
Possible cause of malfunction
Activation of
Protective device in outdoor unit
protective
is activated.
device
Indoor thermistor is either open
Thermistor
or damaged.
fault
1
Outdoor thermistor is either
open or damaged.
2
3
EEP ROM on indoor unit P.C.B. failure
Protective device for compressor
Protective
4
No. 1 is activated.
device for
compressor is
activated
5
Protective device for compressor
No. 2 is activated.
Protective device for compressor
No. 3 is activated.
6
Low oil level.
Oil sensor fault.
(Disconnection, etc.)
7
8
Compressor thermal protector is activated.
Power supply voltage is unusual. (The voltage is more than 260 V
or less than 160 V between L and N phase.)
Incorrect discharge temperature. (Comp. No. 1)
High pressure switch is activated.
Negative (Defective) phase.
O
sensor (detects low oxygen level) activated
2
Compressor running failure resulting from missing phase in the
compressor wiring, etc. (Start failure not caused by IPM or no gas.)
Negative (defective) N phase.
Incorrect discharge temperature. (Comp. No. 2)
Compressor 3 discharge temp. failure
Outdoor unit fan motor is unusual.
Overcurrent at time of compressor runs more than 80Hz (DCCT
secondary current or ACCT primary current is detected at a time
other than when IPM has tripped.)
Inverter for compressor is unusual. (DC compressor does not operate.)
IPM trip (IPM current or temperature)
Indoor coil temp. sensor (E1)
Indoor coil temp. sensor (E2)
Indoor coil temp. sensor (E3)
Indoor suction air (room) temp. sensor (TA)
Indoor discharge air temp. sensor (BL)
Comp. No. 1 discharge gas temp. sensor (DISCH1)
Comp. No. 2 discharge gas temp. sensor (DISCH2)
Outdoor No. 1 coil gas temp. sensor (EXG1)
Outdoor No. 1 coil liquid temp. sensor (EXL1)
Outdoor air temp. sensor (AIR TEMP)
Compressor intake port temperature sensor (RDT)
High pressure sensor
Low-pressure sensor failure
Compressor 3 discharge temp. sensor failure (DISCH3)
Outdoor No. 2 coil gas temp. sensor (EXG2)
Outdoor No. 2 coil liquid temp. sensor (EXL2)
Outdoor heat exchanger 3 gas (inlet) temp. sensor failure (EXG3)
Outdoor heat exchanger 3 liquid (outlet) temp. sensor failure (EXL3)
EEP ROM on the main or sub outdoor unit P.C.B. is a failure.
Overload current is detected.
Lock current is detected.
Current is not detected when comp. No. 1 is ON.
Discharge gas temperature of the comp. No. 1 is not detected.
Temp. sensor is not seated at the sensor holder.
Overload current is detected.
Lock current is detected.
Current is not detected when comp. No. 2 is ON.
Discharge gas temperature of the comp. No. 2 is not detected.
Compressor No. 3 current trouble (overcurrent)
Compressor No. 3 current trouble (locked)
Compressor No. 3 CT sensor disconnected or short circuit
Compressor No. 3 discharge temp. sensor disconnected
Low pressure switch is activated.
Comp. No. 1 oil sensor
Comp. No. 2 oil sensor
Oil sensor (connection) failure
3-46
Control of 3-WAY ECO-i SYSTEM
Alarm
message
P02
P03
P04
P05
P14
P16
P17
P18
P22
P26
P29
H31
<<F01>>
(See Note)
<<F02>>
<<F03>>
<<F10>>
<<F11>>
F04
F05
F06
F07
F08
F12
F16
F17
F22
F23
F24
F25
F26
F29
F31
H01
H02
H03
H05
H11
H12
H13
H15
H21
H22
H23
H25
H06
H07
H08
H27
H28