4. Installation Instructions

4-1. Indoor Unit
AVOID:
Areas where leakage of flammable gas may be expected.
Places where large amounts of oil mist exist.
Direct sunlight.
Locations near heat sources which may affect the per-
formance of the unit.
Locations where external air may enter the room directly.
This may cause "sweating" on the air discharge ports,
causing them to spray or drip.
Locations where the remote controller will be splashed
with water or affected by dampness or humidity.
Installing the remote controller behind curtains or furniture.
Locations where high-frequency emissions are generated.
Places where blocks air passages.
Places where the false ceiling is not noticeably on an
incline.
DO:
Select an appropriate position from which every corner of
1
the room can be uniformly cooled.
Select a location where the ceiling is strong enough to
support the weight of the unit.
Select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
Allow room for operation and maintenance as well as un-
2
restricted air flow around the unit.
Install the unit within the maximum elevation difference
above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in Table 1-1.
Allow room for mounting the remote controller about 1 m
3
off the floor, in an area that is not in direct sunlight nor in
the flow of cool air from the indoor unit. Air delivery will
be degraded if the distance from the floor to the ceiling is
greater than 3 m (for L type, greater than 3.5 m).
Places where optimum air distribution can be ensured.
Places where sufficient clearance for maintenance and
4
service can be ensured. (Refer to the diagram.)
NOTE
Air delivery will be degraded if the distance from the floor to
the ceiling is greater than 3 m (for L type, greater than 3.5 m).
5
6
Floor-Standing, Concealed Floor-Standing Type
Min.
10 cm
7
Horizontal view
8
Min.
10 cm
Min. 100 cm
Min. 100 cm
Vertical view
Fig. 4-4

Ceiling-Mounted Type

Min. n. 25 cm
NOTE
The rear of the indoor unit can be installed flush against the
wall.
Min. n. 50 cm
Concealed-Duct Type
2-Way,
4-Way Semi-Concealed Type
25 cm
25 cm
1-Way Semi-Concealed & Slim Type
Semi-Concealed Type
Ceiling
Min. 5 cm
Obstacle
Air
discharge
Air
intake
Min. 5 cm
Side view
Wall-Mounted Type
*
Min.
15 cm
*
SPW-K075/095/125XH : Min. 5 cm
2-30
Design of 3-WAY ECO-i SYSTEM
Ceiling
Wall
Min. n. 25 cm
Front view
Air
discharge
Air intake
Side view
Max. 25 cm
Obstacle
Fig. 4-1
1 m
25 cm
1 m
1 m
Fig. 4-2
Semi-Concealed Slim Type
Wall
100
cm
20
cm
100
Wall
cm
Fig. 4-3
Min.15 cm
*
Min.
15 cm
Front View
Fig. 4-5
1 m
1 m
20
cm
20
cm