How To Connect Wiring To The Terminal - Sanyo CMH3172A Installation Instructions Manual

Inverter multi split system air conditioner
Hide thumbs Also See for CMH3172A:
Table of Contents

Advertisement

5-4. How to Connect Wiring to the Terminal

Loose wiring may cause the
WARNING
terminal to overheat or result
in unit malfunction. A fire
hazard may also exist. There-
fore, be sure all wiring is
tightly connected.
When connecting each power wire to the corresponding
terminal, follow the instructions "How to connect wiring
to the terminal" and fasten the wire securely tight with
the fixing screw of the terminal plate.
How to connect wiring to the terminal
a) For Indoor Unit
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the wire about 9/32" (7 mm).
See the label (Fig. 26) near the terminal plate.
(2) Using a screwdriver, loosen the terminal screw on
the terminal plate.
(3) Insert the wire and tighten the terminal screw com-
pletely using a screwdriver.
b) For Outdoor Unit
I For solid core wiring (or F-cable)
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the solid wire about 15/16" (25
mm). (Fig. 27)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using the pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the termi-
nal plate and fix it securely with the removed termi-
nal screw using a screwdriver.
I For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the stranded wiring about 3/8"
(10 mm) and tightly twist the wire ends. (Figs. 28
and 29)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring connector.
(Fig. 28)
(4) Place the ring connector wire, and replace and
tighten the removed terminal screw using a screw-
driver. (Fig. 30)
STRIP
SIZE
Twist wire ends
Special
Screw
washer
Ring connector
Wire
23
9/32"
(7 mm) (ACTUAL
SIZE)
Fig. 26
Solid wire
Loop
Insulation
Fig. 27
Stranded wire
Ring
connector
Fig. 28
Fig. 29
Screw and
special washer
Terminal plate
Wire
Fig. 30
Ring
connector

Hide quick links: