Installation Of Connected Schedule Timers; Wiring The Schedule Timer; Before Beginning Wiring - Sanyo SPW-C0705DZH8 Technical Data Manual

3-way eco-i multi system 5 series
Table of Contents

Advertisement

5. Schedule Timer

Installation of Connected Schedule Timers

When installing schedule timers (remote controller switches, system controllers, etc.) onto the wall, use the
method shown in Figs. 3-58 and 3-59.
More than
95 mm
(From wall)
Remote controller
wiring outlet
JIS C8340
Switch box for 1
switch (no cover)
Fig. 3-58

Wiring the Schedule Timer

Before beginning wiring

2
Use 0.5 – 2 mm
wires for field supply wiring.
For inter-unit control wiring, use signal wires that
allow the remote controller wiring to be differentiat-
ed from the power wiring, and take care to prevent
miswiring. (Miswiring will damage the schedule
timer.)
Check that the schedule timer communications
wiring and power wiring are connected correctly.
(Fig. 3-60)
<Basic Wiring Diagram>
Route the A/C inter-unit control wiring for central
control as shown in the figure at right.
The maximum number of indoor units that can be
connected to a single system is 64. The maximum
number of outdoor units is 30.
The maximum number of schedule timer units that
can be connected is 8. (A maximum of 10 schedule
timer units and other central control devices can be
connected.)
More than 125 mm
(For connected
installation)
More than
95 mm
(From wall)
Remote controller
wiring outlet
JIS C8340
Switch box for 2
switches (no cover)
*
For maintenance reasons, leave a gap of 25 mm or more between the
remote controller switch and schedule timer if they are arranged in
parallel above/below each other.
Communications wiring
(Inter-unit control wiring)
Do not allow a screwdriver or other
Pre-
metal object to touch the PCB
cautions
terminals when the power is ON.
Communi-
cations
terminal
Connected device
1
Inter-unit
communication
Timer group setting
2
3
1Gr
fixed
Schedule timer address
5
6
7
1
2
System 1
System 2
Inter-unit control
wiring
1-1
1-2
1-3
2-1
NOTE
Depending on the model of A/C, a local adapter
may be required.
3-89
Control of 3-WAY ECO-i SYSTEM
More than
125 mm
(For connected
installation)
Fig. 3-59
Power wiring
Remote controller
wiring outlet
(remote
Power
controller
terminal
terminal)
All switches are
Permitted items for
OFF when the unit
controller operation
is shipped.
1
: OFF
Permit all modes Permit the below items only
: ON
Prohibited items for controller operation
2
Remote controller
3
(4 wires)
4
Manual
2Gr
3Gr
assignment
fixed
fixed
Current-time synchro-
nization communication
3
4
5
6
7
8
Fig. 3-60
System
3
2-2
2-3
3-1
Schedule timer
Fig. 3-61
1
2
3
4
5
6
7
8