Use the following procedure to reinstall the UPS and transfer the critical
load from Maintenance Bypass (AC Line operation) to the UPS:
Powerware
9 Prestige Series User's Guide (2500/3000 VA)
®
1. Reconnect the battery cabinet to the battery connector on the
UPS rear panel.
2. Switch the circuit breaker on all battery cabinets to the ON (
position.
3. Steps 4 through 8 are for changing the output voltage. The
output voltage is factory-configured for 230V. If you do not
need to change the UPS output voltage, skip to Step 9. Use the
following table to select the correct output voltage according to
your PowerPass Module.
PowerPass Module Model Number
60-Hz PPDM 208: 120/208
60-Hz PPDM 208: 120/240
60-Hz PPDM 208: 120
60-Hz PPDM 240: 120/240
60-Hz PPDM 240: 120
50-Hz PPIM 208 (Model 2500 only)
50-Hz PPIM 220
50-Hz PPIM 230
50-Hz PPIM 240
*
The UPS output voltage should be set according to local mains voltage.
4. Press and hold the Output
Y-cord of the PowerPass Module into the power connectors on
the UPS as shown in Figure 22.
Release the Output
All indicators flash simultaneously.
:
www.powerware.com
UPS Voltage Selection*
Set to 220V for 110/220V PPDM output
Set to 230V for 115/230V PPDM output
Set to 240V for 120/240V PPDM output
Set to 220V for 110V PPDM output
Set to 230V for 115V PPDM output
Set to 240V for 120V PPDM output
Off button while plugging the
Off button when the alarm beeps.
UPS Operation
)
|
208
208
208
208
220
230
240