Installation
Access Cover
Screw
Input Breaker
2
1/2
Input
Conduit Access
Access Cover
Screw
Figure 11. UPS with Hardwired PowerPass Module Rear Panel
40
For PowerPass systems with hardwired outputs, overcurrent protection and suitably
rated disconnect switches for the output AC circuit(s) are to be provided by either the
protected equipment or the customer's distribution panel.
18. Connect standard half-inch conduit through the terminal access
box (see Figure 11) and hardwire to the terminal block. See
Figure 12 for the 60-Hz hardwired PPDM wiring or Figure 13
for the 50-Hz hardwired PPIM wiring.
Line 2/Neutral
Figure 12. 60-Hz Hardwired PPDM Terminal Block
Powerware
C A U T I O N
Input
Ground
Line 1
9 Prestige Series User's Guide (2500/3000 VA)
®
Access Cover Screw
Bypass Switch
Terminal Block
Access Cover
2
1/2
Access
Output
208V/240V
120V
Ground
Neutral
Line 2
Line 1
:
www.powerware.com
Output Conduit