Power Supply; Outputs - GE MIFII GEK-106237P Instruction Manual

Digital feeder protection with recloser
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
2.16.4.1 LOW RANGE
Rated DC Voltage:
Min./Max. DC Voltage:
2.16.4.2 HIGH RANGE
Rated DC Voltage:
Min./Max. DC Voltage:
Rated AC Voltage:
Min./Max. AV Voltage:
Power Consumption:
Proper backup time (date, time and log
memory) without power supply voltage
2.16.5.1 OUTPUT RELAYS
Configuration:
Contact Material:
Maximum Operating Voltage:
Single
Contact Carry Continuous:
Make and Carry:
Breaking:
GEK-106237P
24 to 48 Vdc
19 / 58 Vdc
110 to 250 Vdc
88 / 300 Vdc
110 to 230 Vac @ 50 – 60 Hz
88 / 264 Vac @ 50 – 60 Hz
Max. = 10 W
> 1 week
6 Electro-Mechanical Form C
Silver alloy suited for inductive loads
400 Vac
10 A at 250 Vac. general purpose
¾ HP, 124 Vac
1-1/2 HP, 250 Vac
10A, 250 Vac, 0.4 PF,
B300 pilot duty
30 A
4000 VA
MIFII Digital Feeder Relay
2.16 TECHNICAL SPECIFICATIONS

2.16.4 POWER SUPPLY

2.16.5 OUTPUTS

2
2-27

Advertisement

Table of Contents