GE MIFII GEK-106237P Instruction Manual page 213

Digital feeder protection with recloser
Table of Contents

Advertisement

C.6 ERRORS
C.6ERRORS
When any of the previous commands produce an error in the slave the following frame is received:
ADDRESS
01H
We can receive the following values in the error code field:
C
C-10
FUNCTION + 80 H
COD. ERROR
90H
07H
ILLEGAL FUNCTION
01
ILLEGAL DATA ADDRESS
02
ILLEGAL DATA VALUE
03
SLAVE DEVICE FAILURE
04
ACK.
05
SLAVE BUSY
06
NEGATIVE ACKNOWLEDGE
07
MEMORY PARITY ERROR
08
MIFII Digital Feeder Relay
APPENDIX C
CRC
0DC2H