6.2 OUTPUTS AND LEDS CONFIGURATION (FOR OPTIONS 1 AND 2)
Table 6–2: OUTPUTS AND LEDS ELEMENTS
GROUP
PHASE VIRTUAL TRIPS 1
PHASE VIRTUAL TRIPS 2
ELEMENT VIRTUAL TRIPS
INPUTS/OUTPUTS
MIXED 1
LEDS
6
MISCELLANEOUS 2
MIXED 2
1. A 52a or 52b input must be configured. If there are two inputs configured as 52a and 52b, the relay will not take into account the input
configured as 52a and will act according only to the status of the input configured as 52b.
Virtual trip signals are activated as soon as the protection unit trip conditions are present, independently from the enable
setting. This signal can be used to activate LEDs or auxiliary outputs. If the user wants the protection unit to trip, then the
trip enable setting must be activated. In this case, the relay will activate the trip contact.
6-8
NO DEFINITION
OUTPUT OR LED NOT ASSIGNED
50-1a virtual trip
Virtual trip of Phase A 50P1 element
50-1b virtual trip
Virtual trip of Phase B 50P1 element
50-1c virtual trip
Virtual trip of Phase C 50P1 element
50-2a virtual trip
Virtual trip of Phase A 50P2 element
50-2b virtual trip
Virtual trip of Phase B 50P2 element
50-2c virtual trip
Virtual trip of Phase C 50P2 element
51 a virtual trip
Virtual trip of Phase A 51P element
51 b virtual trip
Virtual trip of Phase B 51P element
51 c virtual trip
Virtual trip of Phase C 51P element
50P1 virtual trip
Trip condition for 50P1 element exists
50G1 virtual trip
Trip condition for 50G1 element exists
50P2 virtual trip
Trip condition for 50P2 element exists
50G2 virtual trip
Trip condition for 50G2 element exists
51P virtual trip
Trip condition for 51P element exists
51G virtual trip
Trip condition for 51G element exists
49 virtual trip
Trip condition for 49 element exists
General virtual trip
Any virtual trip of the above mentioned elements
Input 1
Digital input 1
Input 2
Digital input 2
BKR fail status
Output of the breaker failure to open element, when it is enabled
Breaker closed
Active when the breaker is closed, according to 52a or 52b
2
I
Alarm Status
Output of the I
Cold load pickup
Output of the Cold load pickup element, when it is enabled
EEPROM failure
Active when a failure is detected in EEPROM management
User settings
This element is green when the default settings are active and red when the
user's settings are active
READY
Active when the relay is in service and at least one element has its trip enabled
Autorecloser output
Autorecloser output
ACTIVE GROUP
Group 2 active
Local/Remote
It's Local when the HMI is inside the MAIN SETTINGS, ADVANCED
SETTINGS or OPERATIONS menu
MIFII Digital Feeder Relay
2
counter element
6 I/0 CONFIGURATION
1
GEK-106237P