5.2 MAIN SETTINGS
5.2MAIN SETTINGS
PRODUCT SETUP
Relay Status
Frequency
ModBus Format
Phase CT ratio
Ground CT ratio
HMI Password
Comm Password
Slave Address
Communication Baud rate ---
Communication 2 Baud
rate*
Prefault cycles*
*Only available for option C models. For further information please see APPENDIX E
5
5-2
ENERVISTA MII SETUP
HMI
PRODUCT SETUP
PRODUCT SETUP
Relay Operation
Relay Operation
Frequency
Frequency
---
ModBus Format
Phase CT Ratio
Phase CT Ratio
Ground CT Ratio
Ground CT Ratio
---
HMI Password
---
Comm Password
---
Slave Address
Comm Baud Rate
---
COM2 Baud rate
Prefault Cycles
Prefault Cycles
MIFII Digital Feeder Relay
5.2.1 GENERAL SETTINGS
DEFAULT
RANGE
DISABLE
READY / DISABLE
60 Hz
50/60 Hz
Intel
Intel/Motorola
1
1-4000
1
1-4000
0
0-9999
1
1 – 255
1
1 – 255
9.6
0.3, 0.6, 1.2, 2.4, 4.8,
9.6, 19.2
9.6
0.3,0.6,1.2,2.4,4.8,9.
6,19.2
50
10-140
5 SETTINGS
STEP
NA
NA
NA
1
1
1
1
1
NA
NA
1
GEK-106237P