2 PRODUCT DESCRIPTION

2.13 MEASUREMENT AND SELF-TEST

2.13MEASUREMENT AND SELF-TEST

2.13.1 MEASUREMENT

MIFII provides actual values for phase and ground currents Accuracy is 1% of injected current at rated current, and 3% of
injected current ±0.1% full scale in the complete range.

2.13.2 SELF-TEST

2
Self-monitoring tests are carried out both when the unit is started up and during normal operation. Any internal problem
detected by the self-monitoring function will issue an alarm and the READY output contact will be released, indicating an
out of service condition.