Oscillography Masks; Breaker Failure To Open; Cold Load Pickup - GE MIFII GEK-106237P Instruction Manual

Digital feeder protection with recloser
Table of Contents

Advertisement

5 SETTINGS
OSCILLOGRAPHY MASK

Oscillography masks

Oscillo by communications
Oscillo by digital input
Oscillo by trip
Oscillo by pickup
This option is available only in MIFII models with OPTION 2.
ENERVISTA MII SETUP
Counter
2
Maximum Counter
I
limit
This option is available only in MIFII models with OPTION 2

Breaker failure to open

Breaker failure to open enable
Fail to open timer
This option is available only in MIFII models with OPTION 2

Cold load pickup

Cold load pickup enable
Pickup time
Drop out time
Constant. 50P pickup
Constant 51P pickup
COMMENTS ON SETTINGS:
The factory default HMI password to change any setting is 1. See chapter 8 for details.
The ACTIVE GROUP setting, in the Advanced General Settings, selects which of the two settings groups is active at a
given time. Its default value is 1 (GROUP 1).
The procedure to set the Phase and Ground TOC (Time Delayed Overcurrent) functions (51P / 51N) is the same for both
functions: First, the pickup value must be set (PICKUP); Then, using the CURVE TYPE (current versus time tripping
characteristic curve), the type of time delay preferred is selected, either DEFINITE TIME, or any of the three inverse curves;
If the choice is any of the inverse curves (Inverse, Very Inverse or Extremely Inverse), then the relay takes into account the
TIME DIAL setting, to identify which of the curves in the family must be used (there are 195 different curves for each curve
type, depending on the Time Dial Selected); if the curve type selected is DEFINITE TIME, then the Time Dial setting is
ignored and the time delay used is the one specified in DEFINITE TIME setting.
GEK-106237P
ENERVISTA MII SETUP
Oscillography mask
Oscillo by communic.
Oscillo by Digital Input
Oscillo by trip
Oscillo by pickup
HMI
I^2 MAX Value
2
I
T MAX
ENERVISTA MII SETUP
Breaker failure to open
Breaker failure function
Fail to open timer
ENERVISTA MII SETUP
Cold load pickup
Cold load pickup function
T IN
T OUT
K 50P
K 51P
MIFII Digital Feeder Relay
DEFAULT
NO
NO
NO
NO
DEFAULT
RANGE
999.000
0.000-999.000 kA2
5.3.7 BREAKER FAILURE TO OPEN
HMI
DEFAULT
BF
Function
NO
Delay
400
HMI
DEFAULT
CLP
Function
NO
Outage Time
2.000
On Load Time
2.000
Phase IOC Mult
1.00
Phase TOC Mult
1.00
5.3 ADVANCED SETTINGS
5.3.5 OSCILLOGRAPHY MASKS
RANGE
STEP
Y/N
NA
Y/N
NA
Y/N
NA
Y/N
NA
2
5.3.6 I
COUNTER
STEP
0.001 kA2
RANGE
STEP
Y/N
NA
50-999 ms
1 ms
5.3.8 COLD LOAD PICKUP
RANGE
STEP
Yes/No
NA
0.000-60.000 s
0.001 s
0.000-60.000 s
0.001 s
1.00-5.00
0.01
1.00-5.00
0.01
5
5-11

Advertisement